Enclosure 6N Pressure Switches
Page 7
6.
If you want to check the decreasing setpoint, slowly decrease the pressure or vacuum
after the switch has actuated and note the value at which the audible snap or an
ohmmeter indicates deactuation. Deadband may be calculated if desired by
subtracting the decreasing setpoint reading from the increasing setpoint reading.
7.
On all models except 130P, replace the cover by swinging it back into position over
the adjustment window and tightening the screws until the cover is snug against its
gasket. Do not overtighten, as this could damage the gasket