7

a.

Place cover on flow switch and turn on power. Initiate 
fluid flow through the system. Observe the device being 
activated by the flow switch to determine if device is 
operating as required.

b.

Turn off fluid flow to determine if device is operating 
as required.

c.

Repeat initiating and turning off fluid flow several times to
test flow switch and device for proper operation.
- If operating as required, put system into service.
- If not operating as required, flow switch may need 

to be adjusted.

OFF

ON

STEP 4 - Testing

STEP 5 - Adjustment

FLOW

Adjustment
Lever Screw

Flow
No Flow

0.12
0.06

Flow

No Flow

The Flow Rates Shown
Are Averages, May
Vary –10% 

2.5

1.5

MAXIMUM

ADJUSTMENT

MINIMUM

ADJUSTMENT

Adjustment is necessary only if required flow/no
flow setpoints are above factory set minimum.

a.

Turn off power.

b.

Locate adjustment lever on bottom of unit.
Note that lever will be perpendicular to flow 
switch body.

c.

Loosen adjustment lever screw but DO NOT 
REMOVE.

d.

Turn adjustment lever counter-clockwise to 
increase setpoint. Maximum setting is with 
adjustment lever parallel with flow switch body.

e.

Tighten adjustment lever screw.

f.

Turn on power.

g.

Test the operation of the flow switch after 
each adjustment.

ADJUSTMENT DATA

(All flow rates given in GPM - gallons per minute)

Содержание McDonnell & Miller FS-6 Series

Страница 1: ...an electrical fire or equipment damage electrical wiring insulation must have a rating of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C To prevent electrocution when the electrical power i...

Страница 2: ...ectronic has Type 1C action micro interruption on operation LVD 73 23 EEC EMC 89 33 EEC For applications with loads between 38mA and 3 7 Amps power factors exceeding 0 65 an anticipated system switch...

Страница 3: ...1 Determine the Location of the Flow Switch 5 x D MINIMUM 5 x D MINIMUM D PIPE DIAMETER 3 4 or 1 PIPE D The flow switch should be located in a horizontal section of pipe where there is a straight hori...

Страница 4: ...low switch and one wrench on connecting piping Tighten to following torque values 47 ft lb 64 N m for 3 4 pipe 63 ft lb 85 N m for 1 pipe Repeat to connect pipe to opposite side of flow switch a Apply...

Страница 5: ...trical Installation To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation must h...

Страница 6: ...itch will be used to actuate a signal alarm or other device when no flow occurs connect the wire from that device to the N C contact Connect the Hot power supply wire to C terminal Flow Opens Circuit...

Страница 7: ...FLOW Adjustment Lever Screw Flow No Flow 0 12 0 06 Flow No Flow The Flow Rates Shown Are Averages May Vary 10 2 5 1 5 MAXIMUM ADJUSTMENT MINIMUM ADJUSTMENT Adjustment is necessary only if required flo...

Страница 8: ...tically Solution a Adjustment screw may have been turned below original factory setpoint Verify that flow rate is high enough for flow switch to activate Measure flow rate and match with velocities sh...

Отзывы: