HYDROVAR

Pump Control

Quick Start Guide

Startup of a Hydrovar drive or Packaged Hy-

drovar Pump/Drive. Consult IM223 for recom-

mended system design, including pump, valves, 

transducer, and diaphragm tank. For additional 

applications, consult IM223.

Must be installed by qualified personnel.
1. Align drive on 3 Ph/TEFC motor and attach to mo-

tor using 4 clamps and screws provided. Remove 

cover.

2. Verify power is off before connecting to drive. 

Attach power wires to pump mounted fused 

disconnect (if packaged product) or from wall 

mounted fused disconnect or breaker box. Use 

fast acting Class T fuses. Route wires through 

cable gland, conduit plate – large opening –and 

through cable gland nut. 

3. Attach Power wires to drive: Attach ground wire 

to ground screw. If 1 Ph, attach L and N to ap-

propriately labeled terminals. If 3 Ph, attach wires 

to appropriate L1, L2, L3 terminals. See IOM for 

terminal locations.

1 Ph 2, 3 HP 

3 Ph 3, 5 HP 

3 Ph 7.5, 10, 15 HP

(A)  Power supply 

(B)  Motor 

(C)  Terminal block:

 

 

 

connections 

 

- START/STOP

(D)  RS-485 Interface 

(E)  Status-Relays 

 

- SOLORUN

 

- User interface 

 

 

 

- RS-485 Interface

 

- Internal interface  (F)  Optional 

 

 

 

Relay Card

4. Drive connection to motor: Route wires through 

cable gland and other large conduit opening as 

above. Connect wires to appropriate terminals. 

Use crimp-on spades for sizes 2, 3, 5 HP. Termi-

nate wires at terminals U, V, W for sizes 7.5 HP 

and up. 

*** Route the following low voltage wires 

through small conduit glands and openings as 

needed. ***

5. Attach transducer wires to terminals X3: 1-3; 

Shield, White, Brown respectively.

6. Attach thermal overload switch to motor body at 

conduit box screw, and terminate at the 2 termi-

nals labeled X1 PTC. If not using Thermal over-

load switch, place jumper between PTC terminals. 

7.  Provide Emergency stop switch, or jumper be-

tween terminals X3: 7, 8.

8. Provide additional on/off switch or jumper be-

tween terminals X3: 11, 12 

9. If using multiple communicating drives, attach 

RS485 wires to terminals X4: 4-6, (-, +, Shield 

respectively) on Master drives; X2: 1-3 on Basic 

drives. Daisy chain communication wires starting 

at Master drive to all additional drives. 

10. Verify all connections are secure with no stray 

wires. Attach ground wire from drive to cover 

and replace cover. Note: Be sure cover sits secure-

ly on drive without pinching any wires. Securely 

HAND TIGHTEN cover screws. Cover must be 

firmly attached for buttons to function properly.

11. Connect power. The display should look as 

follows:

12. See attached flowchart for available program-

ming options to change.

13. Push Right arrow to next screen to change Set-

point. Use Up/Down arrows to change setpoint, 

(Required value).

14. Push left arrow once to get back to main screen. 

Push left arrow again to get to Main menu. Use 

Down arrow to scroll through menu options. To 

change any parameter other than set point, you 

must first enter a password. From main menu, 

scroll down to Group 60, and push right arrow 

once to parameter 61. Enter password using up 

arrow key, (password = 66).

15. For multipump programming, change the high-

lighted parameters in the flowchart. Change: 

Parameter 105 to “Cascade Serial”; set the pump 

address to 1, 2, etc in parameter 106.

16. From main screen, press up arrow to start drive. 

Check rotation on pump. Switch 2 of 3 line wires 

from the drive at motor if reverse rotation. 

ITT 

0.0 Hz

STOP 

XXX.X PSI