5.2.3 Final Control
It must be possible to turn the unit easily by hand at the stub shaft.
5.2.4 Mounting of Pump / Unit
The pumps must be bolted to a solid base (e.g. concrete foundation, steel plate, steel bracket, etc.). This
base must withstand all loads occurring during operation. The place, where the pump is mounted must
be prepared acc. to the dimensions of the dimensional drawings. The concrete foundations should have
sufficient firmness acc. to DIN 1045 or equal standard (min. BN 15), to ensure a secure, functional
mounting.
The concrete foundation must have set, before the unit is errected. Ist surface must be horizontal and
even. For the position and size of the pump feet and the foudation screws refer to the dimensional draw-
ing.
Concrete expansion bolts, epoxy capsle anchor bolts or anchor bolts grouted with the foundation (stone
screws), can be used for.
NOTICE:
Sufficient space must be provided for maintenance and repair work, especially for replacing the
drive motor or the complete pump unit. The motor fan must be able to take in enough cool air,
and the intake grille must therefore be at least 10 cm away from any wall, etc.
•
When mounting the pump on the foundation it must be adjusted at the discharge nozzle by means
of a spirit-level (at discharge nozzle). The
permitted deviation is 0,2 mm/m. Levelling shims must be inserted next to the foundation anchors
and must lie plainly.
•
If vibrations are transmitted to the foundation from adjoining components, it must be guarded
through adequate vibration damping paddings (vibrations from outside can impair the bearing).
•
To prevent vibrations being transmitted to adjoining components, the foundation should be laid on a
suitable insulating base.
NOTICE:
The size of these insulating pads will vary, depending on circumstances, and should therefore
be determined by an experienced specialist.
5.2 Piping checklists
24
ICB Installation, Operation and Maintenance Instruction