Section 7, Plumbing the System
International Thermal Research
7-3
Figure 7-1 Heating Module
•
All plumbing lines must be run and secured so as to prevent
damage, chafing and kinking
•
Ensure that the coolant flow is adequate through the POLAR™
HD Heating Module and the system. An indication of inadequate
flow is, when the POLAR™ HD Heating Module is running and up
to normal operating temperature, the difference between the
inlet and outlet coolant temperature to the POLAR™ HD Heating
Module is less than 20F.
•
The Distribution Module contains three distribution pumps and
one heat exchanger and is pre-wired and pre-plumbed for ease
of installation.
•
The Heating and Distribution Modules should be filled and flushed
prior to operation to remove any foreign debris.