Switch Settings
Input / Output Settings SW1
DIP
Switch
Function
ON
OFF
Default
Setting
1-1
Error Reset or Direction input
Error reset
Direction
OFF
1-2
Error recovery
Manual
Automatic
ON
1-3
PNP or NPN output
PNP
NPN
ON
HBL-606FP
OFF
HBL-606FN
1-4
ZPA release mode
Train / Slug
Singulated
OFF
1-5
Motor A direction
Based on MDR type
Based on MDR type
ON
1-6
Motor B direction
Based on MDR type
Based on MDR type
ON
1-7
Zone count
One zone
Two zones
OFF
1-8
Error output function
Pulsed
Signal when error occurs
OFF
DIP switch 1-1 – Error Reset or Direction
•
Error Reset (RST; ON)
o
When the signal is applied then removed it resets an error(s) on all cards connected by communication
cables
•
Direction (DIR; OFF) [Default]
o
Reverses the logic and motor direction while signal is applied to all cards connected by communication
cables
SW 1-5 and 1-6 only change motor direction and do not change logic direction
•
If both signals need to be used
o
Set DIP switch 1-1 ON for one card and input the RST signal to CN4-1 on the same card
o
Set DIP switch 1-1 OFF for another card and input the DIR signal to CN4-1 on the same card
DIP switch 1-2 – Error recovery
•
Manual recovery (MANU; ON) [Default]
o
Some form of user intervention is needed to reset if the card is in thermal protection
o
The temperature of the motor or card must be in operating range in order for the recovery to work
o
Remove power (CN1) to the card, then reapply – most likely case
o
Input then remove a signal to CN4-1 and have DIP switch 1-1 set ON for Error Reset (RST)
This will send an error reset signal through all cards connected by communication cables
o
Input a signal to CN4-2 and have DIP switch 2-3 set ON for forcible run for errors on motor A
This will reset errors for motor A
o
Input a signal to CN4-3 and have DIP switch 2-4 set ON for forcible run for errors on motor B
This will reset errors for motor B
•
Automatic recovery (AUTO; OFF)
o
The card will automatically reset the thermal protection once it or the motor has cooled to operating
temperature.
o
This will also reset a low voltage error once the voltage becomes stable
DIP switch 1-3 – Output signal type for both CN4-5 (OUT A) & CN4-6 (OUT B)
•
PNP (ON) [Default on HBL-606FP]
o
When active the output will be +24V DC
Do not connect to a low impedance input, 0V, or GND
•
NPN (OFF) [Default on HBL-606FN]
o
When active the output will be 0V DC