ITI ESL 562 Скачать руководство пользователя страница 2

2

ESL Smoke Sensor Model 562

Mounting Guidelines

Preliminary

ity roo, and hallways not protected by the required 
smoke alarms. The installation of smoke alarms in 
kitchens, attics (finished or unfinished), or garages is 
not normally recommended, as these locations occa-
sionally experence conditions that can result in 
improper operation.”

The above NFPA standards are a minimum 
requirement for smoke sensor installation. For better 
protection, we also require the installation of a smoke 
sensor inside every bedroom in existing construction.

DO NOT mount a smoke alarm to a drop ceiling tile; 
mount it to a metal runner (see figure 2).

Figure 2. Smoke alarm mounted to drop ceiling.

Mount all smoke alarms within 100 feet of the panel.

Install a minimum of two smoke alarms in any house-
hold, no matter how small it is.

Put a smoke alarm in the hallway outside of every bed-
room area. A minimum of two smoke alarms are 
required in homes with two bedroom areas (see 
figure 3).

A78-1171-02

Figure 3. Residence with multiple sleeping areas

Put a smoke alarm on every level of a multi-level resi-
dence (see figure 4).

Figure 4. Multi-level residence

Install basement alarms on the ceiling at the bottom of 
the basement stairwell.

Install smoke alarms on the ceiling as close to the cen-
ter of the room as possible. If this is not practical, 
install it on the ceiling no closer than 4 inches (10 cm) 
from any wall or corner (see figure 5).

If ceiling mounting is not practical, install on an inside 
wall between 4 and 6 inches (10 and 15 cm) from the 
ceiling (see figure 5).

Put smoke alarms at both ends of a bedroom hallway if 
the hallway is more than 30 feet (9 meters) long. Large 
rooms over 900 square feet require more than a single 
sensor.

Figure 5. Smoke alarm mounting locations

Areas with rough ceilings or short, transom-type walls 
coming down from the ceiling require additional smoke 
alarms.

Install second-floor smoke alarms on the ceiling at the 
top of the first-to-second floor stairwell. Be sure no 
door or other obstruction blocks the path of smoke to 
the unit.

In rooms with sloped, peaked, or gabled ceilings, 
install smoke alarms 3 feet (0.9 meter) measured down 
on the slant from the highest point of the ceiling (see 
figure 6).

Figure 6. Sloped, peaked, or gabled ceilings

Limitations

All alarms are subject to possible compromise or failure-to-
warn for a variety of reasons, for example:

Smoke alarms cannot detect smoke in chimneys, walls, 
roofs, or smoke blocked by a closed door.

Alarms may not detect smoke on other levels of the 
building.

BEDROOM

SMOKE DETECTORS FOR
MINIMUM PROTECTION

SMOKE DETECTORS FOR
MORE PROTECTION AND 
REQUIRED IN NEW CONSTRUCTION

BEDROOM

BEDROOM

LIVING ROOM

DINING

ROOM

KITCHEN

FAMILY ROOM

BEDROOM

BEDROOM

BEDROOM

LIVING

ROOM

KITCHEN

BASEMENT

GARAGE

SMOKE DETECTORS FOR MINIMUM PROTECTION

SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

BEST LOCATION
ACCEPTABLE LOCATION

DEAD AIR

SPACE

BEST IN CENTER

OF CEILING

NO CLOSER THAN 4

" (10 cm)

FROM SIDE WALL

MOUNT ON WALL

AT LEAST 4

" (10 cm)

FROM CEILING

NO MORE

THAN 6

" (15 cm)

FROM CEILING

HORIZONTAL

DISTANCE

FROM PEAK

3 FEET

(.9M)

Содержание ESL 562

Страница 1: ...o add the smoke alarm to panel memory 1 Remove smoke unit from mounting bracket 2 Put the panel in Program Mode Learn Sensors 3 Select a sensor group and sensor number 4 Remove mounting bracket 5 Press and hold the test button 6 The panel will indicate that the sensor has been learned 7 Exit from program mode Note Reinstall smoke unit on mounting bracket Mounting Guidelines Determine the best moun...

Страница 2: ...l install on an inside wall between 4 and 6 inches 10 and 15 cm from the ceiling see figure 5 Put smoke alarms at both ends of a bedroom hallway if the hallway is more than 30 feet 9 meters long Large rooms over 900 square feet require more than a single sensor Figure 5 Smoke alarm mounting locations Areas with rough ceilings or short transom type walls coming down from the ceiling require additio...

Страница 3: ...ut the panel in sensor test mode Although not neces sary for this model it is a good practice to maintain Refer to the specific panel installation instructions for details Simon and Advent panels must be in sensor test If not you will not see anything at the panel WARNING Commander and Caretaker panels will go into alarm if not in sensor test when the test button is pressed 2 Press and hold the te...

Страница 4: ...Notify fire department from a neighbor s phone WARNING If you arrive at the premises and hear sirens do not attemp to enter the building Call for emer gency assistance from a neighbor s phone Floor Plan Example Figure 9 is an example of a multilevel floor plan Use it as a guide and draw your floor plan on the next page Figure 9 Example of a floor plan Your Floor Plan When establishing your excape ...

Страница 5: ...5 ESL Smoke Sensor Model 562 Emergencies Preliminary ...

Страница 6: ... 848 95 Residential Installations UL 268 60 849 95 Commercial Installations This device complies with part 15 of the FCC rules Operation is subject to the following two conditions This device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation Changes or modifications not expressly approved by Interactive Te...

Отзывы: