15
2.5. Capacity
Type S
Capacity (
m3/h
)
Pressure (Pa)
Power (W)
Setting 1 minimum
25
5
1,6
Stand 1 standard
75
11
2,5
Setting 1 maximum
125
31
5,2
Position 2 standard
(*)
150
44
7,3
Setting 3 minimum
175
60
10,2
Stand 3 standard
225
100
18,7
Setting 3 maximum
375
100
50
Type H
Capacity (
m3/h
)
Pressure (Pa)
Power (W)
Setting 1 minimum
25
5
1,6
Stand 1 standard
75
11
2,5
Setting 1 maximum
125
31
5,2
Position 2 standard
(*)
175
60
10,2
Setting 3 minimum
175
60
10,2
Stand 3 standard
275
100
31,6
Setting 3 maximum
415
100
62
*) Position 2 is the automatic position when sensors (
CO2
, RH and/or PIR) are logged in. The capacity is automatically controlled
between low and high.