Electrical installation
Page 88
8.6
Connector: resolver [X2A]
8.6.1
Configuration on the device [X2A]
D-SUB connector, 9-pin type, female
8.6.2
Mating connector [X2A]
D-SUB connector, 9-pin type, male
Housing for a 9-pin D-SUB connector with locking screws of type 4/40 UNC
8.6.3
Pin assignment [X2A]
Table 37:
Pin assignment [X2A]
Pin no.
Name
Value
Specification
1
S2
3.5 V
RMS
/ 5-10 kHz
R
i
> 5 k
Ω
SINE track signal, differential
6
S4
2
S1
3.5 V
RMS
/ 5-10 kHz
R
i
> 5 k
Ω
COSINE track signal, differential
7
S3
3
AGND
0 V
Shield for signal pairs (inner shield)
8
MT-
GND
Temperature sensor reference potential
4
R1
7 V
RMS
/ 5-10 kHz I
out
≤
150 mA
RMS
Carrier signal for the resolver
9
R2
GND
5
MT+
+ 3.3 V / Ri = 2 k
Ω
Motor temperature sensor, normally closed contact, PTC,
KTY…
In addition, the outer cable shield of the angle encoder cable must be connected to the mounting plate of the
controller over a large contact area with the aid of shield terminal SK14.