Installation and operation 

 

5 Installation and operation  

 
5.1 Installation  

 
The device is designed for switch panel mounting in a borehole of Ø22.5 mm (see Annex A for dimensional 
drawings).  
Carefully position the supplied gasket on the display rear surface. Insert the cylindrical part of the device into 
the borehole and tighten the nut from the rear side of the switch panel. Connect the device to the signal ca-
ble in accordance with Annex B.  
The device factory settings can be changed before assembly if necessary. For this purpose the display must 
be connected to a standard signal 4 - 20 mA. 
 
 

 

 
 
 
 

 
 
 
 
 
 
 
 
 

 

 

 

5.2 Operating mode  

 
The operating mode is automatically switched on if the standard signal 4 - 20 mA is connected to the termi-
nals.  
The input signal is digitalised, the square root calculated (if the function is enabled) and the signal according-
ly to the set parameters calibrated and displayed. The scale factor is calculated based on the parameter 

di.Lo 

“lower limit” (according to input signal 4 mA) and 

di.Hi 

“upper limit” (according to input signal 20 mA).  

If the input signal is lower than 3.8 mA, the error message 

Lo 

is displayed.  

If the input signal is higher than 22.5 mA, the error message 

Hi 

is displayed.  

Square root function 

 

This function is intended for transmitters with square characteristic curve. To enable the function, the param-
eter 

Sqrt 

must be set to 

ON

.  

Damping function 

 

Undesirable signal fluctuations can be suppressed through the adjustable filter constant.  

The most important feature of the exponential filters is 

τ

– the filter time constant (parameter 

td

) (see Fig. 3 

and Table 2).  
If the constant increases, the display reacts to changes of the input signal more slowly and the susceptibility 
to interference is lower. 

 

 

Fig. 2 Mounting 1 

Содержание DISPLAY L.P.

Страница 1: ...IMB223 Rev 1 00 Oct 21 DISPLAY L P Digital process display 4 20 mA User manual...

Страница 2: ...4 3 Specifications 5 4 Functional description 6 5 Installation and operation 7 5 1 Installation 7 5 2 Operating mode 7 5 3 Programming mode 9 6 Maintenance 12 7 Transportation and storage 13 8 Packag...

Страница 3: ...operating manual No technical modifications may be made to the device The device may not be used if the environmental conditions temperature humidity etc are not within the limits indicated in the spe...

Страница 4: ...e device includes the control and monitoring of industrial processes The display can be used in automated systems as a primary or secondary display The device may only be operated properly installed a...

Страница 5: ...20 mA Dynamic input resistance 200 Ohm Accuracy 0 2 1 digit Display LED 7 segment display Character height 14 mm Display colour red or green Number of digits in display 4 Sampling rate without dampin...

Страница 6: ...ncreases the speed of pa rameter changing in three steps The operating modes are described in Section 5 The device has the following functions Display physical parameters received from process control...

Страница 7: ...e square root calculated if the function is enabled and the signal according ly to the set parameters calibrated and displayed The scale factor is calculated based on the parameter di Lo lower limit a...

Страница 8: ...IMB223 Rev 1 00 Oct 21 Installation and operation Fig 3...

Страница 9: ...tion on off on oFF Comments 1 Factory settings are highlighted 2 With particular setting parameters the device cannot display the necessary minus sign due to the re striction to four segments The para...

Страница 10: ...IMB223 Rev 1 00 Oct 21 Installation and operation Fig 4...

Страница 11: ...I This means that the upper end of the menu has been reached If the button is pressed while the parameter Sqrt is being displayed the following characters appear on the display I This means that the...

Страница 12: ...ce person nel and comprising the following tasks Removing dust dirt and foreign matter from the housing Checking mounting of device Checking connections The device should be cleaned with a damp cloth...

Страница 13: ...tation and storage The device must be transported in closed transport boxes Protective measures against shocks vibrations and humidity must be observed There may be no chemically active substances in...

Страница 14: ...IMB223 Rev 1 00 Oct 21 Package content 8 Package content Digital process display 1 Gasket 1 Mounting nut 1 User manual 1...

Страница 15: ...IMB223 Rev 1 00 Oct 21 Annex A Dimensions Annex A Dimensions Fig A 1 To prevent the device spinning the borehole in the front panel must correspond to the dimensions in Fig A 2 Fig A 2...

Страница 16: ...IMB223 Rev 1 00 Oct 21 Annex B Electrical connection Annex B Electrical connection Fig B 1 Fig B 2...

Страница 17: ...r technical and editorial errors or omissions in the material contained herein nor for incidental or consequential damages resulting from the supply performance or use of this material Warranty We war...

Отзывы: