6
Function displays in stand-alone and DMX operating mode
LED state
Meaning
1 x LED (red)
OFF
No operating voltage
ON
Operating voltage, no error
1Hz blinking
Too high mains voltage (>400Vs)
1x bl break 1.5s Error in self-test
2x bl break 1.5s
After the ISYGLT dialing (DIP switches) no valid ISYGLT version is recognized
3x bl break 1.5s
No valid parameters available
1 x LED (yellow)
Operating voltage /
BUS
OFF
No BUS signal detected
ON
BUS is active, but communication processor is not receiving data
DMX: Data for the set address are not transmitted (telegram too short) or data format is
wrong
RS-485 test: set address or data format is wrong
1Hz blinking
Communication processor receives data
2 x LED (green)
OFF
Output „OFF“, no error
ON
Output „ON“, no error
1Hz blinking
Warning/switch-off at too high temperatures:
Communication processor: 65°C / 75°C
MOSFET housing: 95°C / 105°C
1x bl break 1.5s
Signal at overload:
1. if the max. permissible peak current (>15A) is exceeded
2. if the limit values for power loss (>8W/channel) or peak current (>10A) are reached
2x bl break 1.5s
Signal after switch-off at voltage peaks >450V
3x bl break 1.5s
Failure of communication with dimmer processor
DIP switches
ISYGLT BUS operating mode
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
Sample address 37
Address 0 to 127
OFF
All OFF
Mode
Address bit
0
1
2
3
4
5
6
ISY
GL
T
PC t
est (RS485/USB)