The manuf
actur
er guar
antees only Engl
ish text a
vailable on our web si
te www
.isoil.com
MAN_MV110_EN_IT_IS_R13_1.04.XXXX
45 / 89
When a measure mass unit is set, the specific gravity function is automatically enabled by the system. Please, note that
the mass measure is heavily affected by the temperature. With certain liquids this may cause significant measurement
errors. The following measure of time units can be selected: s = second, m = minute, h = hour, d = day .
MASS UNIT METRIC
g
Gram
kg
Kilogram
t
Ton
MENU 3 - SCALE
The FS2 (full scale flow rate 2) is active with POS. 6.6 see page 34 ,enabled.
The full scale is used to indicate to the maximum meter’s flow rate. The full scale should be chosen carefully as it’s
parameters are used for several other parameters.There are three fields to fill in order to set this parameter, from left to
right: 1) unit of measure, 2) time unit of measure and 3) numeric value. The selection is made by positioning the cursor
on the field to modify. To change the type unit of measure (metric, Imperial units, mass or volume) see POS. 2.3 see page
and
POS. 2.20 see page 33. The value of Fs1-2 depend nominal diameter POS.
1.4 see page 34. The following tables shown the units of measure available and the conversion factor by comparison
with 1dm3 and 1kg. The converter accepts any kind of combination of units of measure satisfying both the following
conditions:
Numeric field value 99999
1/25 fsmax ≤ numeric field value ≤ fsmax.
Where fsmax is the maximum full scale value corresponding to the sensor, equal to a 10m/s liquid speed. The unit
of measures are shown as appear on the display. The Imperial units units are diversified by using capital and small
characters.
NOT METRIC
in³
Cubic inch
Gal
American gallon
ft³
Cubic foot
bbl
Standard barrel
BBL
Oil barrel
hf³
Hecto cubic feet
KGL
American Kilo gallon
kf³
Kilo cubic feet
ttG
Ten thousand gallons
IGL
Imperial gallon
IKG
Imperial Kilo gallon
Aft
Acre foot
MGL
Mega gallon
IMG
Imperial mega gallon
METRIC
cm³
Cubic centimeter
ml
Milliliter
l
Liter
dm³
Cubic decimeter
dal
Decalitre
hl
Hectolitre
m³
Cubic meter
ML
Mega Liter
MASS UNIT NOT
METRIC
Oz
Ounce
Lb
Pound
Ton
Short tons
(POS. 3.1-2) Flow Rate Full Scale 1-2
[FS1-2= l/s xxxx.x]
AL2
[FRFS1-FRFS2]
The command FRFS1 =? and command FRS2 = ?, edited by MCP software, return a list of only the unit compatible with
the nominal diameter set. If the sensor is insertion type and the diameter is zero, the only possible unit is m/s if the flow
rate were chosen metric units, else f/s for the unit of measurement non metric.
NOTES FOR USING THE MCP INTERFACE