SfAR-S-8AI2DO User Manual
www.ismacontrolli.com
DMP273en | 3rd Issue rev. 2 | 05/2022
page 22 of 26
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
30056
55
0x37
Analog 4
Read
30057
56
0x38
Analog 5
Read
30058
57
0x39
Analog 6
Read
30059
58
0x3A
Analog 7
Read
30060
59
0x3B
Analog 8
Read
30061
60
0x3C
Value of 1. Alarm
Input
Read
Current values of voltage /
current for alarm inputs
30062
61
0x3D
Value of 2. Alarm
Input
Read
40063
62
0x3E
MAX Alarm Level 1
Read/write
If the analog signal
exceeds this value the
corresponding alarm flag
is set
40064
63
0x3F
MAX Alarm Level 2
Read/write
40065
64
0x40
MAX Alarm Level 3
Read/write
40066
65
0x41
MAX Alarm Level 4
Read/write
40067
66
0x42
MAX Alarm Level 5
Read/write
40068
67
0x43
MAX Alarm Level 6
Read/write
40069
68
0x44
MAX Alarm Level 7
Read/write
40070
69
0x45
MAX Alarm Level 8
Read/write
40071
70
0x46
MIN Alarm Level 1
Read/write
If the analog signal is
below this value
corresponding alarm flag
is set
40072
71
0x47
MIN Alarm Level 2
Read/write
40073
72
0x48
MIN Alarm Level 3
Read/write
40074
73
0x49
MIN Alarm Level 4
Read/write
40075
74
0x4A
MIN Alarm Level 5
Read/write
40076
75
0x4B
MIN Alarm Level 6
Read/write
40077
76
0x4C
MIN Alarm Level 7
Read/write
40078
77
0x4D
MIN Alarm Level 8
Read/write
40079
78
0x4E
Alarm Settings 1
Read/write
Alarm settings
0 – alarm due to the
current analog signal
value