SfAR-1M-1AI1DO User Manual
www.ismacontrolli.com
DMP264en | 3rd Issue rev. 1 | 05/2022
page 16 of 19
8 Module Registers
8.1 Registered Access
Modbus
Address
Decimal
Address
Hex
Address
Register Name
Access
Description
30001
0
0x00
Version/Type
Read
Version and type of the
device
30002
1
0x01
Address
Read
Module Address
40003
2
0x02
Baud Rate
Read/write
RS485 baud rate
40004
3
0x03
Stop Bits & Data Bits
Read/write
No. of stop bits & data bits
40005
4
0x04
Parity
Read/write
Parity bit
40006
5
0x05
Response Delay
Read/write
Response delay in ms
40007
6
0x06
Modbus Mode
Read/write
Modbus .ode (ASCII or
RTU)
40010
9
0x09
Filter
Read/write
Measurement filtering,
value from 1 to 10
40033
32
0x20
Received packets LSR
(Least Significant
Register)
Read/write
No. of received packets
40034
33
0x21
Received packets MSR
(Most Significant
Register)
Read/write
40035
34
0x22
Incorrect packets LSR
Read/write
No. of received packets
with error
40036
35
0x23
Incorrect packets MSR Read/write
40037
36
0x24
Sent packets LSR
Read/write
No. of sent packets
40038
37
0x25
Sent packets MSR
Read/write
30051
50
0x32
Inputs
Read
Connected inputs
Bit in high state
→
signal is
connected
40052
51
0x33
Outputs
Read/write
Alarms state
bit no. 3 digital output
30053
52
0x34
Voltage
Read
Voltage in mV
30054
53
0x35
Current
Read
Current in μA or ‰
40055
54
0x36
Alarm – Max Voltage
Read/write
Maximum value of voltage
excess which causes set