iSMA-B-FCU Hardware User Manual
www.ismacontrolli.com
DMP242en | 1st Issue rev. 3 | 02/2022
page 15 of 53
•
•
•
•
•
•
•
The extension communication LED (COM2) lights up (orange) for 20 ms after sending
each package through the extension ports. As long as the module receives/sends
packages, the extension communication LED blinks continuously.
The ALM LED is off by default, the function is programmable through the LED_ALARM
component; it blinks very softly if there is a fault during the start-up of Sedona Virtual
Machine.
During the
device’s
reset, when the 6
th
switch in the S1 - PROTOCOL DIP switch is on
(default settings restoration mode), the power LED (ON) blinks in 300 ms time
intervals. After the switch 6 is switched off, the power LED is lit permanently, and the
default settings are restored.
If the device remains in the bootloader status, the power LED (ON) and the
communication LED (COM1) blink alternatively. The communication LED keeps its
functionality and blinks also after sending/receiving data packages.
4.6.3 DIP Switch
The iSMA-B-FCU controller is equipped with 3 DIP switches:
6-position S1 - PROTOCOL DIP switch;
8-position S2 - MAC DIP switch;
8-position S3 - CFG DIP switch.
S1 PROTOCOL DIP Switch: Baud Rate Selection
Transmission baud rate is determined by S1 switch (sections 1, 2, and 3 of the
PROTOCOL DIP switch) in accordance with the following table.
1
2
3
Baud Rate
Off (0)
Off (0)
Off (0)
Defined by the user
Off (0)
Off (0)
On (1)
76800
Off (0)
On (1)
Off (0)
4800
Off (0)
On (1)
On (1)
9600
On (1)
Off (0)
Off (0)
19200
On (1)
Off (0)
On (1)
38400
On (1)
On (1)
Off (0)
57600
On (1)
On (1)
On (1)
115200
Table 4. Setting baud rate
S1 PROTOCOL DIP Switch: Protocol Selection
Protocol selection is made with sections 4 and 5 of the PROTOCOL DIP switch according
to the table.