Instructions Manual of Communication Interfaces MI485 / MI486 / MI488

 3 

1

 

DESCRIPTION 

1.1

 

MI485 

The MI485 communication interface converts an RS485 signal to an RS232 signal and viceversa. The signals are electrically 
isolated. The communication interface is designed for connecting instruments with RS485 communication to RS232 
communication (a PC, PLC, etc.). The MI485 interface with corresponding equipment enables setting and reading the instruments 
with communication rate up to 115.2  kbps. 

1.2

 

MI486 AND MI488 

MI486 and MI488 communication interfaces are designed for connecting the instruments with RS232 or RS485 communication to 
ethernet network. They enable connection of the instruments with a PC via ethernet network. The signals are electrically isolated. 
The interfaces are designed only for reading data from intruments (with corresponding software). They enable communication rate 
up to 115.2 kbps. 
   

2

 

CONNECTION 

2.1

 

MI485 

Three groups of terminals should be connected to the MI485 communication interface: 

 

Auxiliary power supply: It is connected to terminals 13 and 14. Auxiliary voltage value is written on the interface front 
label. 

 

RS232 communication: Connect it according to the table below. Maximal length is 3 meters. 

MI485 

Computer – DB9 

Tx (26) 

Rx (2) 

Rx (24) 

Tx (3) 

GND (25) 

GND (5) 

 

RS485 communication: It enables connection of up to 32 devices. The line should be terminated with a 120 

 resistor. 

Connection is made according to the table below. 

 

MI485 

RS485 instruments 

A (21) 

DATA + 

B (23) 

DATA - 

 

 

After connection to power  supply voltage, the Power LED indicates the presence of supply, while diodes Rx and Tx indicate data 
transfer. 

2.2

 

MI486 AND MI488 

Three groups of terminals should be connected to the communication interface MI486 or MI488: 

 

Auxiliary power suppy: It is connected to terminals 13 and 14. Auxiliary  voltage value is  written on the interface front 
label. 

 

Ethernet connection: Connect the ethernet cable to 10/100 RJ45 terminal on the communication interface and connect it 
with ethernet network. 

 

RS232 communication (for MI486): Connect it according to the table below. Maximal length is 3 meters (

CROSS-

OVER cable

). 

MI486 

RS232 instruments 

Tx (23) 

Rx 

Rx (21) 

Tx 

GND (22) 

GND 

 

RS485 communication (for MI488): It enables connection of up to 32 devices. The line should be terminated with 120 

 

resistor. Connection is made according to the table below. 

MI488 

RS485 instruments 

A (21) 

DATA + (A) 

B (23) 

DATA – (B) 

Содержание MI485

Страница 1: ...Instructions Manual Communication Interfaces MI485 MI486 MI488...

Страница 2: ...TTING 4 3 1 MI485 4 3 2 MI486 AND MI488 4 3 2 1 SETTING ethernet CONNECTION 4 3 2 2 DeviceInstaller PROGRAM INSTALLATION AND INTERFACE SETTING 5 3 2 2 1 Setting fixed IP address 5 3 2 2 2 Communicatio...

Страница 3: ...alue is written on the interface front label RS232 communication Connect it according to the table below Maximal length is 3 meters MI485 Computer DB9 Tx 26 Rx 2 Rx 24 Tx 3 GND 25 GND 5 RS485 communic...

Страница 4: ...nt addresses set when purchased their address is 33 They should also have the same communication rate at purcase it is 9600 bits s The MiNet program is recommended for parameter setting 3 2 MI486 AND...

Страница 5: ...a CD and choose Setup exe in the Device_Installer directory e g E Device_Installer Setup exe Follow recommended settings by the installation wizard After program installation restart the PC 3 2 2 1 S...

Страница 6: ...MI486 MI488 3 2 2 2 Communication interface configuration 1 Click the selected interface type A window below is displayed 2 Click the Configure icon 3 Your own remarks regarding the interface can be w...

Страница 7: ...6 MI488 7 4 Set communication parameters on the Ports tab 5 Click the Edit Settings key and write required communication parameters WARNING The rate that is set in a window below is a maximal rate for...

Страница 8: ...I486 MI488 6 Set a corresponding local port on the Advanced tab If the communication interface is used together with the Com Port redirector program setting are described in continuation the local por...

Страница 9: ...in MI488 communication interfaces via ethernet networks is also enabled with the programs designed only for communication via serial connection COM 3 2 3 1 Setting of virtual com port 1 Click the Star...

Страница 10: ...nication Interfaces MI485 MI486 MI488 4 Click the Save key in the main dialogue window and confirm the data on the screen In this way the virtual COM port has been successfully set After setting the v...

Страница 11: ...ogram If communication rate of 115200 bitov s is set try to select a smaller rate e g 57600 bits s 4 2 MI486 AND MI488 If communication with the measuring instruments cannot be established check the f...

Отзывы: