background image

UP

UP

9.1 INSTALLATION EXAMPLE: VERTICAL WITH ADHESIVE GASKET (NOT FLAT WALL) 

8. INSTALLATION EXAMPLE: VERTICAL ON A WALL

UP

UP

8.1 INSTALLATION EXAMPLE: HORIZONTAL ON A WALL

7. ELECTRICAL CONNECTIONS EXAMPLE: TO ATLAS BY ETHERNET CABLE

Ethernet cable

FTP AWG24 CAT5E

(Max length 500mt)

R

4

3

2

1

ATLAS PLUS/STD CH1 (J5)
ATLAS DIN CH1 and CH2

R

A

B

Heavy Duty Reader
connector (RS485)

Maximum Ethernet cable length between Atlas and Heavy Duty Reader: 500mt.

Required Atlas power supply: 24Vdc.

Resistance value: 120 ohm (1/4W) on both Atlas and F9000 Reader sides.

Connect the ethernet cable shield to the Atlas GND connector only if Atlas NOT connected to ground.

(GND)

R = 120 ohm (1/4 W)

For more information about Atlas and its connectors, refer ot the 

Atlas Installation Guide 

avalable at:

app.iseo.com

.

Adhesive 

gasket

Back cover 

fixing plate

9. ADHESIVE GASKET USE

WALL

WALL

7.1 ELECTRICAL CONNECTIONS EXAMPLE: TO ATLAS BY ETHERNET CABLE

Ethernet cable

FTP AWG24 CAT5E

(Max length 500mt)

R

4

3

2

1

R

A

B

(GND)

R = 120 ohm (1/4 W)

7.2 ELECTRICAL CONNECTIONS EXAMPLE: TO ATLAS BY ALARM CABLE

Alarm cable (shielded)

4 x 0,35mm - 22AWG

(Max length 100mt)

4

3

2

1

A

B

Required Atlas power supply: 24Vdc.

(GND)

R = 120 ohm (1/4 W)

ATLAS PLUS/STD CH2 (J11)
and CH1 (J5)

ATLAS PLUS/STD CH1 (J5)
ATLAS DIN CH1 and CH2

UP

UP

4

3

2

1

(GND)

4

3

2

1

5
6

CH1 

CH2 

See warnings in box 7

7.3 ELECTRICAL CONNECTIONS EXAMPLE: TO ATLAS BY ALARM CABLE

4

3

2

1

A

B

(GND)

R = 120 ohm (1/4 W)

4

3

2

1

(GND)

4

3

2

1

5
6

CH1 

CH2 

See warnings in box 7.2

Heavy Duty Reader
connector (RS485)

Heavy Duty Reader
connector (RS485)

Heavy Duty Reader
connector (RS485)

ATLAS PLUS/STD CH2 (J11)
and CH1 (J5)

Alarm cable (shielded)

4 x 0,35mm - 22AWG

(Max length 100mt)

Wall fixings not provided in the kit.

Wall fixings not provided in the kit.

Wall fixings not provided in the kit.

Recommended capacitance conductor/conductor < 100pF/m.
Recommended conductors electrical resistance max 90 ohm/Km.

Maximum cable length between Atlas and Heavy Duty Reader: 100mt.
Resistance value: 120 ohm (1/4W) on both Atlas and F9000 Reader sides.

Connect the ethernet cable shield to the Atlas GND connector only if Atlas NOT connected to ground.
For more information about Atlas and its connectors, refer ot the 

Atlas Installation Guide 

avalable at:

app.iseo.com

.

Recommended capacitance conductor/conductor < 100pF/m.
Recommended conductors electrical resistance max 90 ohm/Km.

R

R

R

R

Ethernet cable FTP AWG24 CAT5E (and above).

Shielded alarm cable good quality 4 x 0,35mm (22AWG).

A
B

A

B

A
B

A
B

Отзывы: