background image

Document history

Version

Date

Major changes

2.1

11.03.2020

Safety information, disposal, Intended Use, Adjustment DC output power

2.0

28.02.2017

Relayouted version

Disclaimer / Copyright

Copyright © 2020 by iseg Spezialelektronik GmbH / Germany. All Rights Reserved.
This document is under copyright of iseg Spezialelektronik GmbH, Germany. It is forbidden to copy, extract parts, duplicate for 
any kind of publication without a written permission of iseg Spezialelektronik GmbH. This information has been prepared for 
assisting operation and maintenance personnel to enable efficient use. 

The information in this manual is subject to change without notice. We take no responsibility for any mistake in the 
document. We reserve the right to make changes in the product design without reservation and without notification to 
the users. We decline all responsibility for damages and injuries caused by an improper use of the device.

ECH242 / 244  – 2 / 4 Slot MMS Crate | Last modified on: 11.03.2020| www.iseg-hv.com

2/15

www.iseg-hv.com

Содержание MMS-Crate ECH 242

Страница 1: ...S Crate Series for iseg MMS High Voltage Power Supply Modules up to 4 MMS High Voltage Power Supply Modules 200 300 W power supply wide range of HV modules compatible to CC24 CC23 Controller boards with embedded iCS Linux Server vertical and horizontal desktop use 2 slot version ...

Страница 2: ...on without a written permission of iseg Spezialelektronik GmbH This information has been prepared for assisting operation and maintenance personnel to enable efficient use The information in this manual is subject to change without notice We take no responsibility for any mistake in the document We reserve the right to make changes in the product design without reservation and without notification...

Страница 3: ...afety instructions DANGER DANGER Danger indicates a severe injury hazard The non observance of safety instructions marked as Danger will lead to possible injury or death WARNING WARNING Warning indicates an injury hazard The non observance of safety instructions marked as Warning could lead to possible injury or death CAUTION CAUTION Advices marked as Caution describe actions to avoid possible dam...

Страница 4: ...res on the basis of his technical training his knowledge and experience as well as his knowledge of the relevant regulations General safety instructions Observe the valid regulations for accident prevention and environmental protection Observe the safety regulations of the country in which the product is used Observe the technical data and environmental conditions specified in the product document...

Страница 5: ...lowed to open the unit There are no parts which can be maintained by users inside of the unit Opening the unit will void the warranty WARNING WARNING Before connecting or disconnecting HV cables or any operation on the HV output or the application the unit has to be switched off and discharge of residual voltage has to be finished Depending on application residual voltages can be present for long ...

Страница 6: ...insulation and protective conductor The device may only be operated with the protective earth conductor PE connected The protective conductor connections must be checked for proper function after installation CAUTION Caution When installing the units make sure that an air flow through the corresponding air inlet and outlet openings is possible CAUTION Caution When controlling with software the hig...

Страница 7: ...ons 5 1 General information 8 2 Technical data 8 3 Operation and maintenance 9 3 1 Replacing the fuse 9 3 2 Bridging the internal clamping diode 9 3 3 Forced air cooling 9 4 Compatibility lists 10 5 Dimensional drawings 11 6 Accesories 13 7 Appendix 13 8 Glossary 14 9 Warranty Service 15 10 Disposal 15 11 Manufacturer contact 15 ECH242 244 2 4 Slot MMS Crate Last modified on 11 03 2020 www iseg hv...

Страница 8: ...hernet and WiFi connectivity Up to eight CC23 Slave controller can extend a CC24 system by using galvanically isolated CAN connections and auto adressing 2 Technical data SPECIFICATIONS ECH 242 ECH 244 Slots 2 x MMS modules and 1 x MMS controller 4 x MMS modules and 1 x MMS controller Rated AC mains input 100 240 VAC with PFC 100 240 VAC with PFC AC power connector IEC 320 C14 DC module supply vol...

Страница 9: ...signed to provide an internal GND which is connected with the modules but is galvanically isolated from protective earth and the crate case to avoid ground loops The maximum floating voltage between GND and protective earth is limited by a protection circuit to 47V If necessary the crate GND can be tied hard to protective earth and the housing by bridging the protection circuit on the backplane To...

Страница 10: ...MS HIGH VOLTAGE MODULES NOTES EHS series Standard and High precision CG CFG FG Floating unipolar All series please refer controller manual for firmware requirments EDS series Cost effective distributor module CFG unipolar EBS series Bipolar 4 quadrant module CFG bipolar ESS series High power 2 quadrant module sink and source FG unipolar ECH242 244 2 4 Slot MMS Crate Last modified on 11 03 2020 www...

Страница 11: ...5 Dimensional drawings Figure 2 Dimensional drawing ECH 242 2 channel MMS crate ECH242 244 2 4 Slot MMS Crate Last modified on 11 03 2020 www iseg hv com 11 15 ...

Страница 12: ...Figure 3 Dimensional drawing ECH 244 4 channel MMS HV crate ECH242 244 2 4 Slot MMS Crate Last modified on 11 03 2020 www iseg hv com 12 15 ...

Страница 13: ...0 CANbus Adapter RJ45 to SUB D 9 male Z583382 CANbus Adapter RJ45 to SUB D 9 female Z583401 Genuine power cable EU Plug Z592069 Front panel blind RAL9001 6U 8HP Z514569 Tabelle 3 Accessory items 7 Appendix For more information please use the following download links This document http download iseg hv com SYSTEMS MMS EHS iseg_manual_ECH24x_en pdf Crate Controller CC24 23 manual http download iseg ...

Страница 14: ... Vbounds around Vset Inom nominal output current Iout output current Iset set value of output current Imon monitor voltage of output current Imeas digital measured value of current Itrip current limit to shut down the output voltage Iin input supply current Imax limit max value of output current Ilimit Current Limit Ibounds Current bounds a tolerance tube Iset Ibounds around Iset Pnom nominal outp...

Страница 15: ...port rma 10 Disposal INFORMATION INFORMATION All high voltage equipment and integrated components are largely made of recyclable materials Do not dispose the device with regular residual waste Please use the recycling and disposal facilities for electrical and electronic equipment available in your country 11 Manufacturer contact iseg Spezialelektronik GmbH Bautzner Landstr 23 01454 Radeberg OT Ro...

Отзывы: