background image

S p e z i a l e l e k t r o n i k     G m b H

 

 

 

 

iseg Spezialelektronik GmbH 

Email: [email protected] 

Phone ++ 49 (0)351 / 26 996 - 0 

 

Bautzner Landstr 23 

http://www.iseg-hv.com 

Fax 

++ 49 (0)351 / 26 996 - 21 

 

D - 01454 Radeberg / Rossendorf 

Germany 

 

 
 
Female H15 - connector on the back plane for the HV module 
 

PIN 

Name 

Male H15 - connector / Description 

8 V

REF

 

V

8-10/12 

= 5 V ( 1 mA)   Internal reference voltage for an external potentiometer 

 

 

(Sliding contact on V_V

SET

 or V_I

SET

)) 

10/12  PWR_0V 

Power_0 V (internal connected with HV-GND = LOW-potential) 

14 V_I

MON

 

Monitor voltage corresponding I

OUT

:  

I

OUT

= 0 to I

OUTmax

 

±

 1 % 

 V

14-10/12

 = 0 to 5 V  

20 V_V

SET

 

Setting voltage: V

20-10/12

 = 0 to 5 V   

  V

OUT

 = 0 to V

OUTmax 

±

 1 % 

22 POL 

Polarity switching (TTL level): 

open or  High-level 

 positive, 

  

Low-level 

 negative 

24 V_V

MON

 

Monitor voltage corresponding V

OUT

: V

OUT

= 0 to V

OUTmax

 

±

 1 % 

 V

24-10/12

 = 0 to 5 V  

26 PWR_+V  V

26-10/12

 = + 24 V-DC 

±

 5% / max. 0,8 A 

28 V_I

SET

 

Setting current: 

V

28-10/12

 = 0 to 5 V 

  I

OUT

 = 0 to I

OUTmax

 

±

 1 % 

 

 

 

(connected with V

REF

 through 10 k

    

n.c.: 

I

OUTmax

 is possible 

30 KILL_ENA TTL-level,  High = active 

  HV_OFF without ramp if signal INHIBIT is active. 

Restoring the output voltage is only possible after operating KILL_ENA or PWR_ON. 

 

LOW (or n.c.) 

  HV according V_V

SET

 or V_I

SET

, limited to V

max

, I

max

 resp.

32 INHIBIT  TTL-level,  LOW = active 

  V

OUT

 = 0 

 

HIGH (or n.c.) 

  V

OUT

 according V_V

SET

 (with ramp) 

 
 
Female 96-pin connector for the universal interface board in the crate ECH 128 

         H15-slots from 0 (left ) to 7 (right)                                                        96-pin connector for 
                                                                                                          Multichannel CAN I/O (rightmost)

VS0   to   VS7:    V_v-set   for slots 0 to 7   (H15: 20)

 IS0   to    IS7:     V_i-set    for slots 0 to 7   (H15: 28)

VM0  to   VM7:    V_v-mon for slots 0 to 7   (H15: 24)

IM0   to    IM7:     V_i-mon  for slots 0 to 7   (H15: 14)

KILLEN         :     KILL_ENA for slots 0 to 7 (H15: 30)

            +24 V:     PWR_+V for slots 0 to 7   (H15: 26) 

             GND:      PWR_0V for slots 0 to 7  (H15: 10/12) 

DB0  to   DB7:     POL       for slots 0 to 7   (H15: 22)

 

Содержание ECH 128

Страница 1: ...emoved We decline all responsibility for damages and injuries caused by improper use of the system It is highly recommended to read the operator manual before any kind of operation Note All information in this document is subject to change without notice We take no responsibility whatsoever for any error in this document We reserve the right to make changes in the product design without any notifi...

Страница 2: ...8 slots 7 8TE 40 64mm 1 max 12TE 60 96mm 10 slots 8 TE 40 64mm AC supply voltage Before connecting to the local mains it must be proofed that the nominal line voltage of this unit is equal to the local mains Power Vin 100 240 V AC DC supply voltages 24 V up to 6 25 A 24 V up to 6 25 A Power total max 150 W INHIBIT Lemo hub on the rear connected with INHIBIT signal from all HV modules TTL level LOW...

Страница 3: ...V24 10 12 0 to 5 V 26 PWR_ V V26 10 12 24 V DC 5 max 0 8 A 28 V_ISET Setting current V28 10 12 0 to 5 V IOUT 0 to IOUTmax 1 connected with VREF through 10 kΩ n c IOUTmax is possible 30 KILL_ENA TTL level High active HV_OFF without ramp if signal INHIBIT is active Restoring the output voltage is only possible after operating KILL_ENA or PWR_ON LOW or n c HV according V_VSET or V_ISET limited to Vma...

Страница 4: ...r slots 0 to 7 H15 24 IM0 to IM7 V_i mon for slots 0 to 7 H15 14 KILLEN KILL_ENAfor slots 0 to 7 H15 30 24 V PWR_ Vfor slots 0 to 7 H15 26 GND PWR_0V for slots 0 to 7 H15 10 12 DB0 to DB7 POL for slots 0 to 7 H15 22 H15 slots 0 left to 9 right DB0 to DB7 POL for slots 0 to 7 H15 22 VSO to VS7 IS0 IS1 V_v set for slots 0 to 9 H15 20 IS2 to IS7 V_i set for slots 2 to 7 H15 28 VM0 to VM9 V_v mon for ...