iES10G(F) User Manual
iS5 Communications Inc.
13
connection.
7
PWR2 (N) – Neutral
Connect to the (Neutral) terminal of Power supply
2 the second or backup DC power source.
8
RLY NO
Failsafe Relay, (Normally Open) contact.
9
RLY CM
Failsafe Relay (Common) contact.
10
RLY NC
Failsafe Relay (Normally Closed) contact.
Chassis Ground Connection
The iES10G(F) chassis ground connection, located next to the terminal block, uses a #6-32 Screw.
We recommend terminating the ground connection using a #6 ring lug, and a torque setting of 15
in.lbs (1.7Nm).
3.4
Rear Panel
The components on the rear of the iES10G(F) are shown below:
1.
Screw holes (4) for wall mount kit.
2.
DIN-Rail mount
100-240VAC rated equipment: A 250VAC appropriately rated circuit breaker
must be installed.
Equipment must be installed according to the applicable country wiring codes.
When equipped with a HI voltage power supply and DC backup, independent
sources can be used to power the product for greater redundancy.
120-370VDC rated equipment: A 370VDC appropriately rated circuit breaker
must be installed.
A circuit breaker is not required for DC power supply voltages of 10-48VDC.
For Dual DC power supplies, separate circuit breakers must be installed and
separately identified.
Equipment must be installed according to the applicable country wiring codes.