© IS Technologies Co., Ltd. PAGE
31
/
41
3. Compensation Menu
[P10] Damping Rate
The measured value is not displayed in real time. The value is generated by
average for certain time. It can be more e
ff
ective for accurate value. But when
the level is changed dramatically, it can be inaccuracy. For getting accurate
level, choose the suitable damping rate in accordance with the velocity of
level. The pre-set is “1.”
Option
Description
0.01
0.01m/min
Responds to changes to a max. 0.01m/min (Slow)
Step: 0.01
Minimum: 0.01 - Maximum: 100.0
100.0
100m/min
Responds to changes to a max. 100m/min (Fast)
[P11] Detection Threshold Voltage
This option determines detectable size of return echo. This is useful when the
fi
rst return echo is needed in condition where small objects creating various
kinds of return echoes exist. In case the set value is high, it can be stronger to
the noise, but may not be able to detect small echoes. The 8 is equal to 0.8V.
The table below
sh
ows the equivalent voltage to each value. The pre-set is “3.”
No.
3
4
5
6
7
8
9
10
11
12
13
14
15
Voltage
←
Low High
→
Содержание ULM-1000C
Страница 1: ...IS Technologies Co Ltd PAGE 1 41 Please read this manual attentively before installation...
Страница 5: ...IS Technologies Co Ltd PAGE 5 41 Safety Guide Instruction...
Страница 8: ...IS Technologies Co Ltd PAGE 8 41 Product Description ULM 1000C...
Страница 13: ...IS Technologies Co Ltd PAGE 13 41 INSTALLATION...
Страница 18: ...IS Technologies Co Ltd PAGE 18 41 Wiring...
Страница 20: ...IS Technologies Co Ltd PAGE 20 41 Operation...
Страница 26: ...IS Technologies Co Ltd PAGE 26 41 Programing...
Страница 36: ...IS Technologies Co Ltd PAGE 36 41 Maintenance...
Страница 38: ...IS Technologies Co Ltd PAGE 38 41 Trouble shooting...