background image

3020-dda.ib.rev0.doc 

Page 8 of 17

 09/03/2006

 

Description of operation 

 
See block diagrams commencing on page 4 of this manual. 
 

Input: 

The 155 Mb/s G.703 (STM-1) input signal is connected to the input circuit of the amplifier. 
 
If no power is present then the signal will be directed to the output connector via a relay, RL4. When power is 
applied the relay operates and switches the signal via the amplifier to the second RL4 relay contact and the output 
connectors. 
 
In this power fail mode, the connection from input to output is passive and so only one output can be connected.

 

 

Active path: 

 

Input switching & equaliser: 

The signal from the RL4 relay connects to the input transformer and automatic line equalisation circuit. The purpose 
of this equaliser is to restore both the signal level and the leading and trailing edges of the digital signal so that 
signal jitter is not introduced when the clock signal is derived in the subsequent stage. 

 
Logic processing, reclocking and AIS detection: 

The main logic processing, reclocking, error detection and operational interfacing are all performed by logic circuits 
within a custom-programmed large-scale logic array (FPGA). The internal logic and functions of this IC are too 
complex to describe in detail and the following is intended as a guide to function only. 
 

Data loss detection: 

Valid data is deemed to be present at the module input when 120 or more data pulses have been received in 512 
nominal clock periods. In order for the data pulse to be counted, more than 60% of the minimum anticipated data 
pulse must be present. 
 
If less than 120 data pulses are counted over a period of 512 clock pulses then the data signal is deemed to be 
invalid and the data loss flag is set. 
 
If the area of a given pulse is less than 60% of the minimum anticipated (or acceptable) data pulse, after line 
equalisation and shaping, then that pulse is not considered as a valid input to the count. 
 
In any of these cases the 

Data Loss

 LED on the front panel of the module will light and the general alarm relay 

output will be activated connecting the general alarm output contact to ground. 
 

AIS detection: 

The data processor will detect an incoming AIS (Alarm Indication Signal) (a series of all 1’s in the payload of a 
frame) and will set the AIS flag and the general alarm relay output will be activated connecting the general alarm 
output contact to ground. 
 
The AIS alarm system may be disabled by a link on the main board, LK 3. This prevents the AIS detection from 
operating the automatic changeover function when used in handshake configuration and prevents AIS from setting 
the general alarm output. The AIS detection circuit will, however, still provide AIS indication, on the front panel 
LED, if AIS is detected. 
 
The AIS disable link does not affect the general alarm being activated by data or signal loss as described above. 
 

Power on reset: 

When power is applied to the unit, a 

power on reset

 signal is generated. This signal causes the processing circuit to 

examine its current status and connections and restore operation to its state prior to power failure. 
 
If the DDA is connected for stand-alone operation all alarms will be reset and normal operation will resume. If an 
AIS signal is present on the data input or data is outside the prescribed limits outlined above then the general alarm 
will be activated after the normal detection period has elapsed from the P.O.R. signal being initiated. 
 

Data signal output drivers. 

Four separate output drivers drive the outputs, one of which goes via relay RL4 to O/P 3. In the event of a power 
failure the input is passively switched to O/P 3. 
 
Note that the 

Mon. Output

 on the front panel of the module is obtained in the same manner as the outputs on the rear 

of the module. 

IRT 

Communications 

www.irtcommunications.com

Содержание DDA-3020

Страница 1: ...ustralia IRT can be found on the Internet at http www irtelectronics com I R T Electronics Pty Ltd A B N 35 000 832 575 26 Hotham Parade ARTARMON N S W 2064 AUSTRALIA National Phone 02 9439 3744 Fax 02 9439 7439 International 61 2 9439 3744 61 2 9439 7439 Email sales irtelectronics com Web www irtelectronics com I R T C o m m u n i c a t i o n s w w w i r t c o m m u n i c a t i o n s c o m ...

Страница 2: ...n 17 This instruction book applies to units later than S N 0402001 Operational Safety WARNING Operation of electronic equipment involves the use of voltages and currents that may be dangerous to human life Note that under certain conditions dangerous potentials may exist in some circuits when power controls are in the OFF position Maintenance personnel should observe all safety regulations Do not ...

Страница 3: ... in pairs for redundancy For this configuration the ZDA 3021RH double width rear assembly is needed to link the logic sections of two modules When used as a line equaliser or distribution amplifier the DDA may be housed in any of IRT s standard Eurocard frames When used in pairs for handshake operation only 3 RU chassis types may be used so that the double width rear assembly may be used The DDA 3...

Страница 4: ... DDA SIGNAL PROCESSING JP1 2 JP1 1 JP3 T1 JP2 2 JP2 1 JP3 T2 JP2 3 CHANGE REQUEST JP1 3 O P 1 SK1 O P 4 SK9 O P 3 SK6 O P 5 SK7 GND JP2 4 GND JP1 4 Output Driver FPGA STM1 Generator Change over logic AIS Detector INPUT SK2 RL4 OUTPUTS SK4 Cable EQ PLL MON SK1 Block diagram DDA 3020 Signal path SK6 SK7 Output Driver Output Driver Output Driver Output Driver SK3 RL4 O P 3 O P 4 O P 2 O P 1 RL1 Gener...

Страница 5: ...power has failed General alarm Contact closure to ground if a Data Loss is detected OR b AIS is detected AND the AIS disable link LK 3 is not installed AIS detection is defined as a series of all 1 s in the payload of a frame Data Loss is defined as less than 120 data 1 s in 512 G 703 data rate clock periods Connectors Data BNC Alarm Krone LSA plus Indicators DC power Data loss AIS detect Module i...

Страница 6: ...l of the above cases switching will only occur if companion module is able to provide an output free of the same defects and changeover inhibit switch is not activated on either module Priority logic The priority switching in normal mode follows non reverting logic which dictates In the event of failure of main then standby DDA will assume control and become Main causing the failed path DDA to bec...

Страница 7: ...for successive binary 1s An example is given in Figure A 1 NOTE 1 For binary 0 there is always a positive transition at the midpoint of the binary unit time interval NOTE 2 For binary 1 a there is a positive transition at the start of the binary unit time interval if in the preceding time interval the level was A1 b there is a negative transition at the start of the binary unit time interval if th...

Страница 8: ... pulse after line equalisation and shaping then that pulse is not considered as a valid input to the count In any of these cases the Data Loss LED on the front panel of the module will light and the general alarm relay output will be activated connecting the general alarm output contact to ground AIS detection The data processor will detect an incoming AIS Alarm Indication Signal a series of all 1...

Страница 9: ...te DA selection Handshake mode detection Two data lines are present on the handshake connector to indicate to each module that it is to operate in handshake mode Power on reset When power is applied to the pair the power on reset signal will attempt to reset both modules However as only one module can be Main the logic processor checks for handshake operation and if detected then the module which ...

Страница 10: ...round indicates a loss of input or AIS detection 3 External changeover request connection to ground will make this module Main in handshake mode 4 Ground A third Krone type connector JP3 provides remote status of which unit is In Service Main Pin T1 Connection to ground indicates that module 1 is the In Service Main module T2 Connection to ground indicates that module 2 is the In Service Main modu...

Страница 11: ...tandby on detection of an Alarm Indication Signal AIS OUT Enable switching to Standby on detection of an Alarm Indication Signal AIS Switch settings Sw1 Front panel push button Change request to switch to In Service Main when used with ZDA 3021RH rear assembly Sw2 Front panel slide switch Inhibit Allow request to switch to In Service Main by either Sw1 or loss of signal when used with ZDA 3021RH r...

Страница 12: ... signal earth and chassis earth No attempt should be made to break this connection Installation in frame or chassis See details in separate manual for selected frame type Signal Connections G 703 data connections stand alone operation Connect the input and as many output connections as required Only good quality 75 Ohm connectors and cable should be used The use of 50 Ohm BNC connectors may cause ...

Страница 13: ...information base associated with these devices has the following OIDs Object Identities Alarms In Service or Standby mode State of Change over enable switch State of link that allows or disallows a change to Standby Status on detection of incoming AIS State of link that allows or disallows the transmission of AIS when Input Loss is detected Receive PLL locked input signal present I R T C o m m u n...

Страница 14: ...ANGE DATA LOSS INHIBIT ALLOW MON DDA 3020 DDA 3020 1 2 3 4 JP1 STM1 IN O P 1 O P 4 O P 2 O P 3 BYPASS 1 PWR FAIL 2 GEN ALARM 3 CHANGE REQ 4 GND SK 4 SK 3 SK 7 SK 6 SK 2 ZDA 3021RH T4 T3 T2 T1 JP1 O P 1 O P 2 O P 3 JP3 RL1 JP2 1 PWR FAIL 2 GEN ALARM 3 CHANGE REQ 4 GND T1 R TALLY T2 L TALLY T3 N C T4 GND O P 4 O P 5 4 3 2 1 4 3 2 1 RL2 I P 2 I P 1 SK 8 SK 5 SK 6 SK 7 SK 9 SK 3 SK 4 I R T C o m m u n...

Страница 15: ...e with SNMP The agent therefore acts as an interface between the NMS and the managed devices The NMS sends a request message and control commands for the managed devices to the agent which in turn sends a response message containing information about the managed devices back to the NMS A managed device contains an SNMP agent and resides on a managed network Managed devices collect and store manage...

Страница 16: ...rogram relevant to the module that it is plugged into Depending on the module besides the module identification parameters such as alarm states inputs and controls etc are communicated to the CDM 4000 agent via a data bus on the rear of the frame Thus the CDM 4000 collects information on what is loaded within the frame what positions they occupy and their current status for communication to the NM...

Страница 17: ...ainable from the component supplier Equipment return Before arranging service ensure that the fault is in the unit to be serviced and not in associated equipment If possible confirm this by substitution Before returning equipment contact should be made with IRT or your local agent to determine whether the equipment can be serviced in the field or should be returned for repair The equipment should ...

Отзывы: