INSTALLATION 

Ensure the power has been turned OFF at the circuit 

breaker. 
Prepare the wires with proper length (cut the excessive 

length, if necessary) and strip for connection. Connect 

the sensor wires to the wires of line voltage and load 

according to the above wiring diagram of desired control. 

Carefully bend the wires in the wall box after all wires are 

properly connected. Mount the sensor in the wall box with 

the screws provided. 
Conduct sensor operation test (refer to the TESTING 

section). Replace the wall plate cover after sensor testing 

and setting completed.

1.

2.

3.

4.

WIRING DIAGRAM

Sensor

Red

Black

Black

Hot(Black)

Line

120VAC, 60Hz

Green

Ground

Load

White

White

Neutral(White)

Sensor

Sensor

Red

Red

Black

Black

Black

Hot

(Black)

Line

120VAC, 60Hz

Load

White

White

Neutral

(White)

Green

Ground

Green

Ground

White

The sensor may be available with other control options, 

consult a qualified electrician or contact [email protected] for 

assistance.

NOTE: Connect the 
GREEN wire to the 
GROUND for safety. 

LENS

PUSH-

BUTTON

IR-TEC International Ltd. warranties this product to be free of defects 

in materials or workmanship for a period of five years from date 

of shipment. There are no obligations or liabilities on the part of 

IR-TEC International Ltd. for consequential damages arising out or in 

connection with the use or performance of this product or other indirect 

damages with respect to loss of property, revenue, or profit, or cost of 

removal, installation or reinstallation. 

WARRANTY

Sensor Mode

Push-button Control

Occupancy Sensor

(Auto-ON, Auto-OFF)
 

Occupancy sensor switches the light ON 

automatically when it detects the presence 

of an occupant. The sensor will switch 

the light OFF automatically if no occupant 

activity has been detected before the time 

delay elapses. 

ON

1 2

Vacancy Sensor

(Manual-ON, Auto-OFF)

Vacancy sensor requires the user to 

manually press the push-button to turn ON 

the light. The sensor will switch the light 

OFF automatically if no occupant activity 

has been detected before the time delay 

elapses. 

NOTE -

 The sensor will automatically turn 

ON the light if it detects occupant activity 

within 30 seconds after time delay elapsed.

Presentation Mode

Pressing the push-button during occupied 

state will turn OFF the load immediately and 

hold off until the push-button is pressed 

again.

In Presentation Mode (PM), pressing 

the push-button will turn OFF the lights 

immediately, and the lights will remain off 

even if motion is detected. Pressing the 

push-button again will turn the light ON and 

the sensor will operate per its settings. If the 

time delay expires and no occupant activity 

has been detected, the sensor will return to 

its normal operation. The lights will turn on 

with the next motion detected.

SW1=ON

Manual ON/OFF

 

 

ON

1 2

SW1=OFF

ON

1 2

SW2=ON

ON

1 2

SW2=OFF

OPERATION

The LBS-701 series wall switch sensor employs passive 

infrared (PIR) sensing technology to monitor the occupancy 

status within its coverage, and control the connected load as 

per sensor setting. The sensor can be programmed to control 

the load as an Occupancy Sensor or Vacancy Sensor via 

setting DIP switch #1. The push-button operation can be 

programmed to turn the load ON and OFF manually or in 

Presentation Mode (PM) for specific requirement via setting 

DIP switch #2. 

This is the delay time that the LBS-701 series sensor will hold 

the load on after the last motion detected. The factory setting is 

10 minutes, and it can be changed by pointing the arrowhead 

of potentiometer to the specific position.  

TIME - Delay time

This is the threshold of ambient light level that the LBS-701S 

sensor will inhibit switching on the load. The factory setting is 

ALS disabled (24 Hr) for ease of testing, and it can be changed 

by pointing the arrowhead of potentiometer to the specific 

position. 

LUX – Ambient light level 

(LBS-701S only)

TESTING

Restore line voltage power for the sensor at circuit breaker.

 

An LED behind the sensor lens will blink to indicate the 

motion sensed.
Replace the wall plate cover after completing sensor testing 

and setting.  

1.
2.

3.

NOTE: The connected load will be switched on as delay time 

set (factory default 10 minutes) once apply the power. The delay 

time can be set to the shortest (10 seconds) for ease of testing. 

Ensure to set the TIME as desired for optimum operation 

after testing. 

LUX

1

7

2

6

3

5

4

TIME

1

7

2

6

3

5

4

LUX

TIME T

POS. 1

2

3

4

5 6

7

1’ 3’ 5’ 10’ 20’ 30’

5 10 30 50 100 150 24H

Factory Set

To change the sensor 

operation mode or  

settings, press the 

push-button cover 

and slide it down as 

shown.

The LBS-701S features ambient light sensor to inhibit 

unnecessary lighting when ambient light is higher than the 

level set. The time delay (TIME) and ambient light level (LUX) 

settings can be changed by rotating the respective Accu-Set 

potentiometer at different positions.

   

SETTING

3-Way Control

Single-Pole Control

Slide

ON

1 2

LUX

TIME

Press

&

ON

1 2

LUX

TIME

DIP

Switch