background image

The LBS-701 is a member of IR-TEC’s WALLSENZR family of 
line voltage wall switch sensor designed to fit in a standard 
NEMA wall box. The sensors combine state-of-the-art passive 
infrared (PIR) sensing technology with décor aesthetics to 
provide optimal energy-saving for all applications. 
   
The sensor will turn ON the load automatically when it detects 
the presence of an occupant, and will turn OFF automatically 
if no motion is detected before the delay time elapses. To 
meet compliance of specific energy code, such as CA Title 
24, the LBS-701 series can be easily programmed as a 
Vacancy sensor. In Vacancy mode, the sensor will only turn 
ON the load by pressing the push-button manually and will 
turn OFF the load automatically per the sensor time delay. 
The LBS-701 allows for the push-button operation to be 
programmed with different manual control options.  

The model LBS-701S comes with an ambient light sensor 
(ALS) to inhibit the lighting if ambient light levels are higher 
than required. The Accu-Set digital potentiometers make 
delay time (TIME) and ambient light level (LUX) settings fast, 
easy and accurate. Zero-crossing relay switching control 
allows the LBS-701 series to control various types of lighting 
and loads safely and effectively.
 

SPECIFICATIONS 

INSTALLATION INSTRUCTIONS

LBS-701 Series

Power supply

Infrared sensor
Zero crossing
Detectable speed
Mounting height

Ambient light level
Delay time setting
Op. humidity
Op. temperature
Dimensions

Detection coverage

Maximum load

120VAC, 60Hz
CFL/Ballast Electronic (LED) – 500W 
Incandescent/Halogen – 600W
Fluorescent Ballast – 700W
Motor – 1/4 HP
Dual element pyroelectric
Automatic frequency detection
1~10 ft./sec. (0.3~3 m/sec)
3 ~ 5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft H
Minor motion- 20 ft x 20 ft (W x L) @4 ft H
7 levels, from dark to 24Hr, LBS-701S only 
T/1’/3’/5’/10’/20’/30’, T=10 sec. for testing 
Max. 95% RH
-40°F ~ 131°F (-40°C ~ 55°C)

4.13”H x 1.77”W x 1.65”D (w/mounting plate) 

INDOOR USE ONLY
Utilisation a L'interieur Uniquement

DETECTION COVERAGE

Top view

Side view

Minor motion

40’

4’

7’

30’

40’

20’

20’

Major motion

The sensor is more sensitive to the movements “crossing” 
the detection zones than “toward” or “away” the sensor. 
To obtain better sensitivity, ensure the sensor to have clear 
field of view for the occupant’s motion within the desired 
coverage. 

The closer movement is to the sensor, the more sensitive 
the sensor is. 

The sensor should be mounted within the specified 
mounting height for optimal performance. 

Avoid blocking the sensor with any obstacles, such as 
door, plant, partition or furniture. As a general rule, every 
occupant within the desired range should be able to 
clearly see the sensor.

Do NOT mount the sensor directly above or nearby a heat 
source, or where unintended motion (e.g. hallway traffic) 
will be “seen” by the sensor. 

1.

2.

3.

4.

5.

P/N: 058-70100-003

Printed in Taiwan

www.irtec.com

This product may be covered by one or more U.S. patents or patent applications.

Please visit www.irtec.com for more information.

INSTALLATION NOTES

OVERVIEW

AVERTISSEMENT & PRUDENCE

WARNING & CAUTION

Risk of Electric Shock - 
Disconnect power supply before servicing.
DO NOT 
control a load in excess of specified ratings to avoid 
damaging the sensor or the property. 
Install and use this sensor in accordance with electrical codes and 
regulations.

 
This device is intended to be installed by a qualified electrician. 
DO NOT attempt to service or repair.

COUPER LE COURANT AU DISJONCTEUR AVANT D'INSTALLER 
LE CAPTEUR ET CABLAGE!
NE PAS contrôler une charge supérieure à la capacité spécifiée pour 
éviter d'endommager le capteur ou la propriété.
Installer et utiliser ce capteur conformément aux codes et règlements 
électriques.
Ce dispositif est destiné à être installé par un électricien qualifié. NE 
PAS tenter de réparer.

Line Voltage Wall Switch Sensor

Отзывы: