The LBS-701 is a member of IR-TEC’s WALLSENZR family of
line voltage wall switch sensor designed to fit in a standard
NEMA wall box. The sensors combine state-of-the-art passive
infrared (PIR) sensing technology with décor aesthetics to
provide optimal energy-saving for all applications.
The sensor will turn ON the load automatically when it detects
the presence of an occupant, and will turn OFF automatically
if no motion is detected before the delay time elapses. To
meet compliance of specific energy code, such as CA Title
24, the LBS-701 series can be easily programmed as a
Vacancy sensor. In Vacancy mode, the sensor will only turn
ON the load by pressing the push-button manually and will
turn OFF the load automatically per the sensor time delay.
The LBS-701 allows for the push-button operation to be
programmed with different manual control options.
The model LBS-701S comes with an ambient light sensor
(ALS) to inhibit the lighting if ambient light levels are higher
than required. The Accu-Set digital potentiometers make
delay time (TIME) and ambient light level (LUX) settings fast,
easy and accurate. Zero-crossing relay switching control
allows the LBS-701 series to control various types of lighting
and loads safely and effectively.
SPECIFICATIONS
INSTALLATION INSTRUCTIONS
LBS-701 Series
Power supply
Infrared sensor
Zero crossing
Detectable speed
Mounting height
Ambient light level
Delay time setting
Op. humidity
Op. temperature
Dimensions
Detection coverage
Maximum load
120VAC, 60Hz
CFL/Ballast Electronic (LED) – 500W
Incandescent/Halogen – 600W
Fluorescent Ballast – 700W
Motor – 1/4 HP
Dual element pyroelectric
Automatic frequency detection
1~10 ft./sec. (0.3~3 m/sec)
3 ~ 5 ft. (90~150 cm) above the floor
Major motion - 30 ft x 40 ft (W x L) @4 ft H
Minor motion- 20 ft x 20 ft (W x L) @4 ft H
7 levels, from dark to 24Hr, LBS-701S only
T/1’/3’/5’/10’/20’/30’, T=10 sec. for testing
Max. 95% RH
-40°F ~ 131°F (-40°C ~ 55°C)
4.13”H x 1.77”W x 1.65”D (w/mounting plate)
INDOOR USE ONLY
Utilisation a L'interieur Uniquement
DETECTION COVERAGE
Top view
Side view
Minor motion
40’
4’
7’
30’
40’
20’
20’
Major motion
The sensor is more sensitive to the movements “crossing”
the detection zones than “toward” or “away” the sensor.
To obtain better sensitivity, ensure the sensor to have clear
field of view for the occupant’s motion within the desired
coverage.
The closer movement is to the sensor, the more sensitive
the sensor is.
The sensor should be mounted within the specified
mounting height for optimal performance.
Avoid blocking the sensor with any obstacles, such as
door, plant, partition or furniture. As a general rule, every
occupant within the desired range should be able to
clearly see the sensor.
Do NOT mount the sensor directly above or nearby a heat
source, or where unintended motion (e.g. hallway traffic)
will be “seen” by the sensor.
1.
2.
3.
4.
5.
P/N: 058-70100-003
Printed in Taiwan
www.irtec.com
This product may be covered by one or more U.S. patents or patent applications.
Please visit www.irtec.com for more information.
INSTALLATION NOTES
OVERVIEW
AVERTISSEMENT & PRUDENCE
WARNING & CAUTION
Risk of Electric Shock -
Disconnect power supply before servicing.
DO NOT control a load in excess of specified ratings to avoid
damaging the sensor or the property.
Install and use this sensor in accordance with electrical codes and
regulations.
This device is intended to be installed by a qualified electrician.
DO NOT attempt to service or repair.
COUPER LE COURANT AU DISJONCTEUR AVANT D'INSTALLER
LE CAPTEUR ET CABLAGE!
NE PAS contrôler une charge supérieure à la capacité spécifiée pour
éviter d'endommager le capteur ou la propriété.
Installer et utiliser ce capteur conformément aux codes et règlements
électriques.
Ce dispositif est destiné à être installé par un électricien qualifié. NE
PAS tenter de réparer.
Line Voltage Wall Switch Sensor