Installation
32
RT-SVX45F-EN
Note:
If digit 9 in the unit model number equals “E”
(electromechanical control), accessory relay
BAY24X042 is required if the thermostat does not
energize the fan circuit in the heating mode.
Table 3.
Zone sensor module wiring
Distance from Unit to
Control
Recommended Wire Size
0 - 150 feet
22 gauge
0 - 45.7 m
.33 mm2
151 - 240 feet
20 gauge
46 - 73.1 m
.50 mm2
241 -385 feet
18 gauge
73.5 - 117.3 m
.75 mm2
386 - 610 feet
16 gauge
117.7 - 185.9 m
1.3 mm2
611 - 970 feet
14 gauge
186.2 - 295.7 m
2.0 mm2