background image

Manual

Status display: 

During normal operation, the yellow LED lights up when the switching output is active. 
During the teach-mode the LED flashes with different frequencies and thus displays the respective mode.  

Factory settings: 

After the initial startup, the sensor has the following default settings: 
switching distance: approx. 65mm sensing 

Description of the teach modes: 

To start the teach process, connect the white wire (PIN 2) with the operating voltage. 
If this connection exists between 3 and 6 seconds, the yellow LED will flash with a frequency of 5Hz. 

After releasing the connection, the teach mode „sensing function“ is active.  
If  this  conection  exists  between  6  and  10  seconds,  the  yellow  LED will  flash  with  a frequency of 2.5Hz. 

After releasing the connection, the teach mode „window function“ is active.  
If the connection exists more than 10 seconds, the device will be reset to the factory settings. The yellow 

LED flashes with a frequency of 0.5Hz. 

Teach process for sensing function 

1. Connect  for  a  period  of  time  between 3 and 6 seconds the  white  wire (PIN 2) with the 

operating voltage. The LED flashes with approx. 5Hz.

2. Release the connection. The yellow LED now flashes with a frequency of 0.3Hz.
3. Place the object to be detected at the desired distance in front of the sensor.
4. Connect the white wire (Pin 2) for at least 1 second with the operating voltage. If the LED lights up 

at that time, the switching output functions as normally open contact (output  is active  when 

object  is  detected).  If  the  LED  is  off  at  that  time,  the switching output functions as normally 

closed contact (output is active, when object is not detected).

5. If the yellow LED flashes with a frequency of 2.5Hz, the teach process was successfull. You can 

release  the  connection  now.  The  taught  value  is  stored  and  is  also  available after switching the 

sensor off and on again.

6. If the LED flashes with a frequency of 6Hz, the teach process has failed. The  object  could not  be 

detected,  beacuse  it  was  e.g.  placed beyond the detection range. In this case, the teach process 

has to be repeated.            

MANUAL • Subject to alteration! Version: 

August  2019

 

ipf electronic gmbh • Rosmarter Allee 14 • 58762 Altena 

 Tel +49 2351 9365-0 • Fax +49 2351 9365-19 

 [email protected] • www.ipf-electronic.com 