Optional teach-in methods, configurable via IO-Link: 

Window-mode:  Level 1 / 1-point teach:   set a window of ± 10% around the position of the object. 

 

 

Level 2 / 2-point teach: 

set a window within the object is being detected. 

Dynamic Teach-In: 

Available also for window mode.  Enter teach level 1 to start the data acquisition and TAP to stop 
the data acquisition (duration 2 … 15s). The switchpoint or window is defined by the detected 
min & max value. 

 

Teach-in instruction 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SAFETY WARNINGS:  

Before initial operation, please make sure to follow all safety instructions that may be provided in the product 
information! 
Never use these articles in applications where the safety of a person depends on their functionality. 

Enter teach level  
-

 

Place  a  ferromagnetic  tool  as 
shown right or connect teach-in 
wire +Vs. 

-

 

Green and yellow LED light up, if 
tool  /  teach-in  is  recognized 
properly. 

-

 

Remove tool after n seconds for 
desired level 

A TAP is a short touch of the tool 
as shown right. 

General information 
-

 

5min after power up the teach with tool 
will be locked.  

-

 

In  teach  mode  the  output  changes  to 
0V. 

-

 

During operation the teach wire should 
be connected to 0V. 

-

 

For external teach-in connect the teach 
wire to +Vs. 

-

 

External teach-in is always possible (no 
locking) 

-

 

Place  tool  >  2sec:  Leave  teach-in 
without changes.

   