Optional teach-in methods, configurable via IO-Link:
Window-mode: Level 1 / 1-point teach: set a window of ± 10% around the position of the object.
Level 2 / 2-point teach:
set a window within the object is being detected.
Dynamic Teach-In:
Available also for window mode. Enter teach level 1 to start the data acquisition and TAP to stop
the data acquisition (duration 2 … 15s). The switchpoint or window is defined by the detected
min & max value.
Teach-in instruction
SAFETY WARNINGS:
Before initial operation, please make sure to follow all safety instructions that may be provided in the product
information!
Never use these articles in applications where the safety of a person depends on their functionality.
Enter teach level
-
Place a ferromagnetic tool as
shown right or connect teach-in
wire +Vs.
-
Green and yellow LED light up, if
tool / teach-in is recognized
properly.
-
Remove tool after n seconds for
desired level
A TAP is a short touch of the tool
as shown right.
General information
-
5min after power up the teach with tool
will be locked.
-
In teach mode the output changes to
0V.
-
During operation the teach wire should
be connected to 0V.
-
For external teach-in connect the teach
wire to +Vs.
-
External teach-in is always possible (no
locking)
-
Place tool > 2sec: Leave teach-in
without changes.