INSTRUCTION MANUAL
C-103EM
Turbo Sleuth Ground Fault Locator
9 September 2002
9
7.5. Wrap the TS-SENSOR loop around all three phases conductors of the circuit. Any imbalance
will be evident in meter deflection when the range is set to the appropriate setting. The ground
fault current pulses will be visible in the meter deflection. Analog meters provide easier reading
during rapid pulsing. The pulse rate may be programmed to facilitate easier readings on digital
meters.
7.6. When placing the sensor around the three phase conductors make sure that the arrow moulded
into the sensor loop points downstream (toward the load) in order to provide proper readings.
7.7. Ensure that the junction point of the loop is held a minimum of 1” away from the conductors in
order to minimize interference.
7.8. Additional information on the TS-SENSOR is available on the TS-SENSOR data sheet and at
the address located at the end of this manual.
Figure 5 : Control Relays
8. Pulse Duration
8.1. Pulse time duration may be varied by programming the LOGO logic controller. This is located
beside the DGF-CT-A. See Figure 5. On the front of the LOGO are four arrow shaped buttons
and two square buttons labelled “ESC” and “OK”. Modify the pulse time settings by following
this procedure.
Ground
Fault
Detector
DGF-CT-A
Pulse
Frequency
Relay
LOGO