background image

 

BMA_77024-180-11_s4 DC_en_Rev1 

IPAS GmbH, Hölscherstraße 27, D-47167 Duisburg 

[email protected] 

Operating- and mounting instructions 

PowerBlock s4 DC 
Order number: 77024-180-11 

 

General usage 

 
Power Block series consists of different devices types for switching of 
power and shutter control. The PowerBlock s4 DC comes in a 4 unit 
DIN rail housing and can be installed in a standard distribution board. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
A brief overview of the functionality is given in the following table: 
 
 
Shutter channel outputs with objects for: 
• 

Facade control 

• 

True height positioning for shutter/blind 

• 

Shutter slits control 

• 

Central Up/Down functions 

• 

Lmits, scenes, presets, alarms, disable function, manual 
control etc. 

 
 
Advanced objects and functions such as: 
• 

Timers (with cyclic sending of time remaining) 

• 

Logic functions (Boolean, gate and filter functions, 
comparators, math.), data point conversion 

• 

KNX scenes (with delays between events) 

• 

Setpoints 

• 

Analogue and digital alarms 

• 

Overwrite end-user parametersrr  

• 

Etc.  

 
 

Scope of delivery 

 
The following individual components are included in the delivery of the 
PowerBlock device: 
 

Complete device with inserted bus connector 

Operating and mounting instructions 

1x heat shrinkable tubing 1.2 x 2cm for additional insulation 
of the bus cable 

Delivered in break-proof individual packaging 

 
 

Application programs 

 
The following application programs are currently available for the 
PowerBlock device: 
 

77024-PowerBlock s4 DC-11-0110 

Installation device 

 

 

 

 
Risk of death by electric shock.  
 

 

The device is intended for interior installation in dry rooms. 

 

The device must only be installed and commissioned by an 
accredited electrical engineer. 

 

When planning and construction of electrical installations, the 
national guidelines, rules and regulations of the country in quest-
ions are to be obeyed, as well as all current KNX guide lines. 

 

For the installation the device must be switched to zero potential. 

 

The device must not be opened.  

 

Any faulty device is to be sent together with a return delivery to 
the manufacturer. 

 

Technical data 

 

POWER AND OUTPUTS SPECIFICATIONS 
Power supply 

 

Supply Voltage: 
Max. Consumption: 
Additional power 
supply: 
 

21..30VDC 
9,4mA  
No 

Number of outputs 

Total outputs 

4 outputs for DC 
shutter control 
with separated 
supply inputs 

Rated Operational 
Voltage 

Shutter 

24V DC 

Rated Current 

Per Channel 

6A 

Load Type 

 

Motor 24V DC 

Output life 
expectance 

Mechanical: 
 
Electrical: 

> 5𝑥10

6

 

operations (at 180 
times/min) 

> 1𝑥10

5

 cycles 

with 10A load 

Connections 

KNX bus connection 
terminal: 
Terminal screw block: 
Tightening torque for 
terminal screw: 

 
0,8 mm Ø solid 
max. 6 mm Ø solid 
 
maximum 0.6 Nm 

GENERAL SPECIFICATIONS 
Control and display 
elements 

 

Programming button: 
 
LED, red: 
 
8 x buttons: (for 
manual channels 
control) 
8 x LEDs, red: 

To assign the 
physical address 
Displays 
addressing mode 
 
To Move Up/Down  
 
To display actual 
outputs/channels 
status  

Mechanical data 

REG casing 4TE: 
Width: 
Hight: 
Lenght: 
Weight 
Mounting: 

Plastic ABS 

– V0 

  72 mm 
  58 mm 
  90 mm 
235 g 
35 mm DIN rail  

Electrical safety 

Pollution class: 
Protection type:* 
Protection class:** 
Overvoltage category: 
KNX Bus: 


IP20 
III 
III 
SELV DC 30V 

EMC requirements 

Complies with: 
 

EMC directive 
2014/30/EU 

Environmental 
conditions 

Weather resistance: 
Environmental con-
ditions in operation: 
Storage emperature: 
Transportation 
temperature: 
Rel. humidity: 
(non condensing) 

EN 50090-2-2 
 
  -5°C to +45°C  
-25°C to +55°C 
    
-25°C to +70°C 
   5 % to 93 % 

Certification CE-
Signage 
  

KNX registered: 
According to EMC-
Guidelines: 

Yes 
(Residential and 
commercial 
buildings), Low 
Voltage guidelines 

 
* (according to EN 60529); ** (according to IEC 1140) 

Отзывы: