Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 10/16

 

UMA-CDZ-IP-ACOWM200-00

 

d1 

Select evaporator sensor 

[1]

 

0 : disable 

1 : enable 

d2 

Temperature calibration of evaporator sensor 

[1] 

-10 / +10°C 

0°C 

°C/°F 

-20 / +20°F 

d4 

Defrost cycle

 

0 / 60 

0: cancel defrost 

function

 

30min 

d7 

Maximum defrost time

 

1 / 99 

20 

min 

d8 

Defrost stop temperature 

0 / +45°C 

7°C 

°C/°F 

+32 / +115°F 

A1 

Compressor start and stop in the mode of “run/stop 

in a proportional time”

 

00 : disable 

01 : enable 

01 

A2 

Compressor start time in case of cabinet sensor 

fault

 

01 /60 

10 

min 

A3 

Compressor stop time in case of cabinet sensor 

fault

 

01 /60 

20 

min 

A4 

Buzzer switch 

[2] 

0 : disable 

buzzer beeping 

1 : enable 

buzzer beeping

 

A5 

Lower alarm. Min temp alarm value 

-50°C/A6

 

-50°C 

°C/°F 

58°F/A6

 

A6 

Higher alarm. Max temp alarm value 

A5/90°C 

90°C 

°C/°F 

A5/194°F 

A7 

Temperature alarm override 

0/60 

20 

min 

A8 

Power-ON alarm override 

0/60 

40 

min 

U1 

Select temperature display sensor 

[1]

 

00 : display 

cabinet sensor 

01 : display 

evaporator 

sensor 

U2 

Switch between Fahrenheit and Celsius 

[3]

 

00 : Fahrenheit 

01 : Celsius 

01 

U3 

Select defrost or light relay function 

00 : defrost out. 

01 : light output 

00 

 

[1]: 

no evaporator sensor available 

[2]: 

no buzzer available 

[3]: 

After switch between Celsius/Fahrenheit, the temperature set-point of parameter item St automatically adjusts to the 

corresponding temperature value of Celsius/Fahrenheit, and the temperature set-points of other parameter items related 

to Celsius/Fahrenheit automatically adjust accordingly.  

For example, St is set to 0

, and it will automatically adjust to 32

 after switch; C4 (calibration value of cabinet sensor) 

is set to +8

,and it will automatically adjust to +20*(8/10)=+16

Suggestion: Switch Celsius/Fahrenheit first, then adjust the value of related parameter items to ensure correct parameter 

configuration. 

 

Button name  Function 

Action 

Set 

Set parameters 

Press it for 3 sec. 

Switch between menu and parameters 

Press it and the 

controller responds. 

 

 

Содержание IP-ACOWM200

Страница 1: ...00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM200 IP ACOWM200 0X Document UMA CDZ IP ACOWM200 00 Date Name Description Original user s manual for air con...

Страница 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Страница 3: ...IP ACOWM200 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 2000 2100 A35 A50 W 1200 1250 Absorbed electric power EN14511 A35 A35 W 1060 1100 A35 A50 W 1240 1300...

Страница 4: ...y GENERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized...

Страница 5: ...IR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM200 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accide...

Страница 6: ...nscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because th...

Страница 7: ...ush the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner si...

Страница 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM200 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM200 IP ACOWM200 0X...

Страница 9: ...nimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan turn...

Страница 10: ...ide 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost...

Страница 11: ...er selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting...

Страница 12: ...if parameter U1 1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFE...

Страница 13: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Страница 14: ...E LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40...

Страница 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM200 00 SAA CERTIFICATE...

Страница 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM200 00 NOTES...

Отзывы: