Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
Page 10/16
UMA-CDZ-IP-ACOWM200-00
d1
Select evaporator sensor
[1]
0 : disable
1 : enable
0
-
d2
Temperature calibration of evaporator sensor
[1]
-10 / +10°C
0°C
°C/°F
-20 / +20°F
d4
Defrost cycle
0 / 60
0: cancel defrost
function
0
30min
d7
Maximum defrost time
1 / 99
20
min
d8
Defrost stop temperature
0 / +45°C
7°C
°C/°F
+32 / +115°F
A1
Compressor start and stop in the mode of “run/stop
in a proportional time”
00 : disable
01 : enable
01
-
A2
Compressor start time in case of cabinet sensor
fault
01 /60
10
min
A3
Compressor stop time in case of cabinet sensor
fault
01 /60
20
min
A4
Buzzer switch
[2]
0 : disable
buzzer beeping
1 : enable
buzzer beeping
0
-
A5
Lower alarm. Min temp alarm value
-50°C/A6
-50°C
°C/°F
58°F/A6
A6
Higher alarm. Max temp alarm value
A5/90°C
90°C
°C/°F
A5/194°F
A7
Temperature alarm override
0/60
20
min
A8
Power-ON alarm override
0/60
40
min
U1
Select temperature display sensor
[1]
00 : display
cabinet sensor
01 : display
evaporator
sensor
0
-
U2
Switch between Fahrenheit and Celsius
[3]
00 : Fahrenheit
01 : Celsius
01
-
U3
Select defrost or light relay function
00 : defrost out.
01 : light output
00
-
[1]:
no evaporator sensor available
[2]:
no buzzer available
[3]:
After switch between Celsius/Fahrenheit, the temperature set-point of parameter item St automatically adjusts to the
corresponding temperature value of Celsius/Fahrenheit, and the temperature set-points of other parameter items related
to Celsius/Fahrenheit automatically adjust accordingly.
For example, St is set to 0
℃
, and it will automatically adjust to 32
℉
after switch; C4 (calibration value of cabinet sensor)
is set to +8
℃
,and it will automatically adjust to +20*(8/10)=+16
℉
.
Suggestion: Switch Celsius/Fahrenheit first, then adjust the value of related parameter items to ensure correct parameter
configuration.
Button name Function
Action
Set
Set parameters
Press it for 3 sec.
Switch between menu and parameters
Press it and the
controller responds.