IP Enclosures IP-ACOWM145 Скачать руководство пользователя страница 11

Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 11/16

 

UMA-CDZ-IP-ACOWM145-00

 

Button name

 

Function

 

Action

 

 

Adjust menu and parameters 

Press it and the 
controller responds. 

 

Adjust menu and parameters 

Press it and the 
controller responds. 

 

Exit setting parameters 

Press it and the 
controller responds. 

 
Set-point adjustment 

 

1)  Press the 

Set

 button for 3 sec in status of measuring and controlling to enter user menu, the panel 

will display 

St

.  

2)  Press the 

Set

 button again to display the parameter value of 

St

, and modify the temperature set-

point by pressing 

 or  . 

WARNING:

 temperature which unit starts to work is St+C1. For example: St=31, C1=4 compressor and 

condenser fan turn on at 35°C (31°C+4°C) 
 

Parameter adjustment 

 

1)  When 

St

 shows, press 

 to display 

Po

, and press 

Set

 to display 

00

; at this moment, use the 

button 

 or   to input the password of administrator menu (

55

).  

2)  After inputting the password 

55

, press 

Set

 to display 

Po

. The controller will automatically verify 

whether the password is correct.  

3)  When it passes verification, press 

 or   to select parameter items 

St, Po, C1, C2……

 (i.e. 

any parameter item of user menu and administrator menu); otherwise, the controller will only stay at 
the parameter items St and Po without displaying other parameter items. 

4)  After selecting the menu, press 

Set

 to enter the current menu and set its parameters. Use 

 or   

to adjust parameter values, then press 

Set

 again to return to menu selection status. 

5)  Under any parameter setting status, press 

 or press no button for 30 sec to exit parameter setting 

and save the current parameter value automatically. 

 

Note: The password of administrator menu is valid for once. After exiting parameter settings by 
pressing 

, correct password must be entered again before adjusting parameters. 

 
View temperature 
 

1)  When 

U1 

(temperature display)

 =

00, the controller displays the current temperature of cabinet 

sensor.  

2) 

When 

U1

=01, the controller displays the current temperature of evaporator sensor. 

 

(WARNING: no evaporator probe available on air conditioner) 

 
Control output 

 

Cooling: 

In normal status: 
Refrigeration starts when the cabinet temperature > temperature set-point 

St

 + control differential 

C1

, and 

the indicated time must elapse between two successive minimum switch-on of the compressor. 
Refrigeration stops when the cabinet temperature < temperature set-point 

St

 
In case of cabinet sensor fault, 
When 

A1

=0, compressor start and stop time in the mode of “run/stop in a proportional time” is disabled, 

refrigeration stops. 
When 

A1

=1, compressor start and stop time in the mode of “run/stop in a proportional time” is enabled, 

refrigeration performs in cycle according to the set refrigeration start 

A2

 and stop 

A3

 time in the mode of 

“run/stop in a proportional time”. 

 

Содержание IP-ACOWM145

Страница 1: ... 00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM145 IP ACOWM145 0X Document UMA CDZ IP ACOWM145 00 Date Name Description Original user s manual for air conditioner IP ACOWM145 series Language English ISSUE 23 05 2021 REV 01 REV 02 REV 03 ...

Страница 2: ...nclosure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary weight of installed AIR CONDITIONER Installation position of AIR CONDITIONER must be selected to ensure good ventilation Take care that any internal external components of enclosure don t obstruct air ...

Страница 3: ... IP ACOWM145 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 1450 1500 A35 A50 W 1150 1200 Absorbed electric power EN14511 A35 A35 W 660 700 A35 A50 W 800 860 Rated current A 3 7 4 2 Motor circuit breaker Delayed pre fuse advised A 10 Electrical connection Three pole connector Air flow rate free blow enclosure m3 h 600 625 Operating temperature ambient C F 5 55...

Страница 4: ...ly GENERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized according to air conditioner dimensions and weight Electrical enclosure must have at least IP54 protection degree Internal and external components of electrical enclosure don t have to affect the pro...

Страница 5: ...AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM145 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accidental injuries ...

Страница 6: ...unscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger evaporator and then it becomes water water production decreases during air conditioner working because enclosure air becomes dry The encl...

Страница 7: ...Push the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner side must be guaranteed Install the delayed fuse recommended on rating plate pasted on air conditioner side to protect the line and enclosure components against short circuit Upstream of the electrical...

Страница 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM145 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM145 IP ACOWM145 0X ...

Страница 9: ...inimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan turn OFF when internal enclosure temperature decreases below set point value 4 1 DIGITAL THERMOSTAT Indicator Symbol Status Meaning Set set On Set parameters Off Measuring controlling Cooling On Cooling s...

Страница 10: ...ride 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost or light relay function 00 defrost out 01 light output 00 1 no evaporator sensor available 2 no buzzer available 3 After switch between Celsius Fahrenheit the temperature set point of parameter item...

Страница 11: ...ter selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting status press or press no button for 30 sec to exit parameter setting and save the current parameter value automatically Note The password of administrator menu is valid for once After exiting parame...

Страница 12: ...1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFERRED TO WIRING DIAGRAM DESCRIPTION CODE 1 Evaporator fan VCENT190D230V 2 Compressor BSD122DT 3 Condenser fan VCENT190D230V C1 Evaporator fan capacitor CON2UFS2M8F C2 Compressor capacitor CON20UFS2M8F C3 Condenser fan ...

Страница 13: ...ooling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This warranty shall become null as soon as the product is altered or modified in its structure or in circuits The terms of this warranty commencement and termination dates are not modified by any repair or...

Страница 14: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40 2003 A1 A2 IEC 60335 2 40 2002 A1 A2 EN 60335 1 2010 A11 A13 A14 A1 A2 IEC 60335 1 A1 A2 OTHER STANDARDS APPLIED EN 55014 1 2017 EN 55014 2 2015 EN IEC 61000 3 2 2019 EN 61000 3 3 2013 Date Name Des...

Страница 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM145 00 SAA CERTIFICATE ...

Страница 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM145 00 NOTES ...

Отзывы: