Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 11/16

 

UMA-CDZ-IP-ACOWM085-00

 

Button name

 

Function

 

Action

 

 

Adjust menu and parameters 

Press it and the 
controller responds. 

 

Adjust menu and parameters 

Press it and the 
controller responds. 

 

Exit setting parameters 

Press it and the 
controller responds. 

 
Set-point adjustment 

 

1)  Press the 

Set

 button for 3 sec in status of measuring and controlling to enter user menu, the panel 

will display 

St

.  

2)  Press the 

Set

 button again to display the parameter value of 

St

, and modify the temperature set-

point by pressing 

 or  . 

WARNING:

 temperature which unit starts to work is St+C1. For example: St=31, C1=4 compressor and 

condenser fan turn on at 35°C (31°C+4°C) 
 

Parameter adjustment 

 

1)  When 

St

 shows, press 

 to display 

Po

, and press 

Set

 to display 

00

; at this moment, use the 

button 

 or   to input the password of administrator menu (

55

).  

2)  After inputting the password 

55

, press 

Set

 to display 

Po

. The controller will automatically verify 

whether the password is correct.  

3)  When it passes verification, press 

 or   to select parameter items 

St, Po, C1, C2……

 (i.e. 

any parameter item of user menu and administrator menu); otherwise, the controller will only stay at 
the parameter items St and Po without displaying other parameter items. 

4)  After selecting the menu, press 

Set

 to enter the current menu and set its parameters. Use 

 or   

to adjust parameter values, then press 

Set

 again to return to menu selection status. 

5)  Under any parameter setting status, press 

 or press no button for 30 sec to exit parameter setting 

and save the current parameter value automatically. 

 

Note: The password of administrator menu is valid for once. After exiting parameter settings by 
pressing 

, correct password must be entered again before adjusting parameters. 

 
View temperature 
 

1)  When 

U1 

(temperature display)

 =

00, the controller displays the current temperature of cabinet 

sensor.  

2) 

When 

U1

=01, the controller displays the current temperature of evaporator sensor. 

 

(WARNING: no evaporator probe available on air conditioner) 

 
Control output 

 

Cooling: 

In normal status: 
Refrigeration starts when the cabinet temperature > temperature set-point 

St

 + control differential 

C1

, and 

the indicated time must elapse between two successive minimum switch-on of the compressor. 
Refrigeration stops when the cabinet temperature < temperature set-point 

St

 
In case of cabinet sensor fault, 
When 

A1

=0, compressor start and stop time in the mode of “run/stop in a proportional time” is disabled, 

refrigeration stops. 
When 

A1

=1, compressor start and stop time in the mode of “run/stop in a proportional time” is enabled, 

refrigeration performs in cycle according to the set refrigeration start 

A2

 and stop 

A3

 time in the mode of 

“run/stop in a proportional time”. 

 

Содержание IP-ACOWM085

Страница 1: ...00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE OUTDOOR APPLICATION IP ACOWM085 IP ACOWM085 0X Document UMA CDZ IP ACOWM085 00 Date Name Description Original user s manual for air con...

Страница 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Страница 3: ...IP ACOWM085 0X FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 850 900 A35 A50 W 625 650 Absorbed electric power EN14511 A35 A35 W 490 530 A35 A50 W 600 640 Rated cu...

Страница 4: ...ERAL CHECKS electrical enclosure must be disconnected form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized accor...

Страница 5: ...IR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACOWM085 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accide...

Страница 6: ...nscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because th...

Страница 7: ...ush the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner si...

Страница 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACOWM085 00 3 1 WIRING DIAGRAM 3 1 1 IP ACOWM085 IP ACOWM085 0X...

Страница 9: ...minimum interval of two successive switch on of the compressor parameter C2 is elapsed Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan tur...

Страница 10: ...ide 0 60 40 min U1 Select temperature display sensor 1 00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost...

Страница 11: ...er selecting the menu press Set to enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting...

Страница 12: ...rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPARE PARTS LIST REFERRED TO WIRING DIA...

Страница 13: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Страница 14: ...E LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 40...

Страница 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACOWM085 00 SAA CERTIFICATE...

Страница 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACOWM085 00 NOTES...

Отзывы: