Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 9/16

 

UMA-CDZ-IP-ACIWM035.001-00

 

4 - STARTING AND ADJUSTMENT 

 
After finishing assembly of the conditioner, wait approx. 30 min. before starting it (the oil 
must collect in the compressor to ensure lubrication and cooling). 
 
The air conditioner operates automatically, that is to say, after insertion, the evaporator fan 
operates continuously making the air inside the cabinet circulate. This way a uniform 
distribution of temperature inside the cabinet itself is attained. The built-in thermostat 
drives compressor and condenser fan according to set point value. 
  

Compressor and condenser fan turn ON when internal enclosure temperature rises 
up to set point value + hysteresis and the minimum interval of two successive 
switch-on of the compressor (parameter C2) is elapsed. 
 
Compressor and condenser fan turn OFF when internal enclosure temperature 
decreases below set point value. 
 
 

1.1  DIGITAL THERMOSTAT 

 

 

 

Indicator 

Symbol 

Status 

Meaning 

Set 

set 

On 

Set parameters 

Off 

Measuring & controlling 

Cooling 

 

On 

Cooling starts 

Off 

Cooling stops. 

Flash 

Cooling delays. 

 

Parameter list 
 

Menu 

Function 

Setting range  Default 

Unit 

St 

Temperature set-point

 

C5 / C6 

31°C 

°C/°F 

Po 

Admin. password

 

0 / 99 

55 

C1 

Temperature differential

 

1 / 15°C 

4°C 

°C/°F 

1 / 30°F 

C2 

The minimum interval of two successive  

switch-on of the compressor

 

1 / 60 

min 

C4 

Temperature calibration of cabinet sensor 

-10 / +10°C 

0°C 

°C/°F 

-20 / +20°F 

C5 

Lower set-point. Min possible set-point 

-50°C/(C6-1) 

20 

°C/°F 

58°F/(C6-1) 

C6 

Higher set-point. Max possible set-point 

(C5+1)/90°C 

45 

°C/°F 

(C5+1)/194°F 

d1 

Select evaporator sensor 

[1]

 

0 : disable 

1 : enable 

Содержание IP-ACIWM035.001

Страница 1: ...001 00 USER S MANUAL PART 2 AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIWM035 001 Document UMA CDZ IP ACIWM035 001 00 Date Name Description Original user s manual for air conditi...

Страница 2: ...enclosure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary...

Страница 3: ...thermostat IP ACIWM035 001 FEATURES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 350 370 A35 A50 W 200 220 Absorbed electric power EN14511 A35 A35 W 290 320 A35 A50 W 320...

Страница 4: ...ed form power supply electrical data shown on rating label pasted on air conditioner side must be guaranteed Electrical enclosure must be sized according to air conditioner dimensions and weight Elect...

Страница 5: ...CONDITIONER FOR ELECTRICAL ENCLOSURE Page 5 16 UMA CDZ IP ACIWM035 001 00 2 3 FITTING 1 Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid acci...

Страница 6: ...unscrewing included in mounting kit 5 Connect the condensate drain pipe like is shown in picture below Put some glue on aluminium pipe before to insert it Air conditioner produces condensate because...

Страница 7: ...Push the spring with a screwdriver and then insert the wire 2 Check the proper wire insertion 3 Connect the unit with the power supply Electrical data shown on rating label pasted on air conditioner...

Страница 8: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8 16 UMA CDZ IP ACIWM035 001 00 3 1 WIRING DIAGRAM 3 1 1 IP ACIWM035 001...

Страница 9: ...lue hysteresis and the minimum interval of two successive switch on of the compressor parameter C2 is elapsed Compressor and condenser fan turn OFF when internal enclosure temperature decreases below...

Страница 10: ...00 display cabinet sensor 01 display evaporator sensor 0 U2 Switch between Fahrenheit and Celsius 3 00 Fahrenheit 01 Celsius 01 U3 Select defrost or light relay function 00 defrost out 01 light output...

Страница 11: ...o enter the current menu and set its parameters Use or to adjust parameter values then press Set again to return to menu selection status 5 Under any parameter setting status press or press no button...

Страница 12: ...ted to show shown if parameter U1 1 rH when temperature A6 and alarm delay time run out controller will display rH rL when temperature A5 and alarm delay time run out controller will display rL 5 SPAR...

Страница 13: ...cooling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This...

Страница 14: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2...

Страница 15: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 15 16 UMA CDZ IP ACIWM035 001 00 SAA CERTIFICATE...

Страница 16: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16 16 UMA CDZ IP ACIWM035 001 00 NOTES...

Отзывы: