More Examples of Control Outputs
Detection on an Analog Input, DAC and P2C Updates
Update Mode: Update on True and False
Criteria: Ch 5 example: Below Limit; Ch 4 example: Inside Window
In this example Channel 5 has been programmed with reference to one setpoint [Limit A], defining a low
limit; and Channel 4 has been programmed with reference to two setpoints [Limits A and B] which define
a window for that channel.
Channel
Condition
State of
Detect Signal
Action
True
When Channel 5 analog input voltage is below the limit A,
update DAC1 with Output Value 0.0V.
5
Below Limit A
(for Channel 5)
False
When the above stated condition is false, update DAC1 with
the Output Value of
minus
1.0V.
True
When Channel 4 analog input voltage is within the window,
update P2C with 70h.
4 Within
Window
(Between Limit A
and Limit B) for
Channel 4
False
When the above stated condition is false (Channel 4 analog
input voltage is outside the window) update P2C with 30h.
Limit A
(for Channel 5)
DAC1
Detection
(for Channel 5)
Limit A
(for Channel 4)
Limit B
(for Channel 4)
P2C
Detection
Signal
(for Channel 4)
Analog Inputs with Setpoints
Update on True and False
DaqBoard/3000 Series User’s Manual
887794
Setpoint Configuration for Output Control 6-7
Содержание DaqBoard/3000USB Series
Страница 2: ...ii...
Страница 8: ...IG 2 968492 DaqBoard 3000USB Series Installation Guide...
Страница 26: ...IG 20 968492 DaqBoard 3000USB Series Installation Guide...
Страница 62: ...4 2 Calibration 897494 DaqBoard 3000 Series User s Manual...
Страница 94: ...6 12 Setpoint Configuration for Output Control 887794 DaqBoard 3000 Series User s Manual...