Page 3
FIXTURE
TSPL
LUMINAIRE HOUSING
STEP 2 -
MOUNTING THE P-32
STEP 3 -
INSTALLING THE TEST SWITCH PILOT LIGHT (TSPL)
RED
WHITE
NEUTRAL
120/277 LINE
UNSWITCHED
BLACK
YELLOW
YEL/BLK
BLU/WHT
BLUE
WHT/RED
EMERGENCY
BALLAST
A. Position the
P-32
in the fixture wireway and fasten securely through the Mounting Slots. If necessary, drill holes and
mount with sheet metal cutting screws (not provided).
B. Fully plug the
Quick Disconnect Harness
into the
P-32
Quick Disconnect Port. Inspect that the Harness is squarely
seated against the
P-32
housing.
C. Attach the flat wire tie holder to the fixture channel. Insert a wire tie into the wire tie holder and pull the wire tie tight
around the wires extending from the Quick Disconnect Harness. This will help prevent the Quick Disconnect Harness
from being disengaged. Inspect that the Quick Disconnect Harness is still fully plugged in to the
P-32
Port.
A. Locate a suitable location for the TSPL and cable that is at least 1” from the fixture lamps and is visible outside the fixture.
Drill or punch a 1/2” diameter hole in the fixture wall or wireway cover. Insert the TSPL into the hole so that the LED test
button/pilot light is located outside of the fixture.
B. Slide the TSPL Mounting Clip firmly to lock and secure the TSPL assembly.
DO NOT CONNECT THE TSPL PLUG AT THIS TIME
STEP 4 -
WIRING THE AC INPUT
The P-32 requires an
unswitched AC input
of 120/277 volts. Connect the
BLACK
wire to the
120/277 Line
, and the
WHITE
wire to the
Neutral
.
COMPLETING INSTALLATION
A
A
B
B
C
P-32
Coming Soon