IOTA IQ-TURBO Скачать руководство пользователя страница 2

BULK STAGE

 - During this state, the charger will operate either at Full Current output or Constant 

Voltage output depending on the discharged state of the battery. A discharged battery will dictate 
the voltage and force the charger into constant-current operation. As the battery charges, the char-
ger transitions to a constant-voltage operation. This BULK STAGE will continue for 240 minutes. At 
this point, the BULK STAGE will switch to the ABSORPTION STAGE.

ABSORPTION STAGE

 - This state is limited to 120 minutes (2 hours) during which the charger 

will operate either at Full Current output or Constant Voltage output depending on the discharged 
state of the battery. During Full Current output, the charger is providing its full current rating and will 
slowly increase the battery voltage to the “Absorption Stage” voltage. At the end of the 120 minutes, 
the charger will revert to the FLOAT STAGE.

FLOAT STAGE

 - This charge state holds the batteries at Constant Voltage for a period not longer 

than seven days. During this state, the charger not only floats the batteries, but it can also provide 
load current up to its maximum rating for other loads without depleting the battery capacity.  The 
FLOAT STAGE will end when either the battery voltage drops below the “Low Trigger” point or at 
the end of 7 days when the IQ-TURBO initiates the MAINTENANCE stage to ensure a complete 
charged condition. In either situation, the unit exits the FLOAT STAGE and enters the BULK STAGE.

FAULT STATE

 - If the IQ enters a FAULT state, its circuitry is automatically disabled. In this state, 

the functionality of the IQ is completely disabled, the LED will flash irregularly, and the charger re-
verts to a stand-alone FLOAT STATE voltage. The unit will not exit this stand-alone FLOAT STATE, 
therefore the unit must be reset by following the steps below.

1. Unplug the charger from its AC source.
2. Disconnect the [+] positive cable from the battery.
3. Wait 30 seconds before reconnecting the input and output. To avoid arcing, it is recom-
mended that the charger be connected to the AC input FIRST before connecting the output 
of the charger to the battery*. 

*Note that the connection sequence of the input and output covered above is recommended every 
time an operator connects the charger to the batteries. However, as long as the charger remains 
connected to the battery, periodic unplugging of the AC input does not require this sequence.

The LED indicator will remain lit or flashing when the charger is unplugged or disconnected from 
the AC supply (de-energized). During this time, the IQ continues to monitor the battery voltage. If 
the battery voltage drops below a pre-determined voltage (Refer to 

Figure D

 for predetermined val-

ues), the IQ will automatically initiate the smart-charging cycle once the AC input is re-connected.

IRREGULAR FLASHING LED

 - If the LED is flashing irregularly or intermittently, then the IQ has 

entered a FAULT state due to a voltage irregularity. When this occurs, the IQ must be re-set in order 
to resume normal operation. Refer to the FAULT STATE instructions below for re-setting procedures.

OPERATION AND LED INDICATOR REFERENCE (cont.)

CHARGING STAGE DESCRIPTIONS

Figure D: Predetermined Stage Trigger Values

68412-110  REV 1800

PREDETERMINED VARIABLES FOR OPERATION

Battery
Voltage

12V
24V

BULK

14.78V
29.56V

ABSORPTION

14.51V
29.02V

FLOAT

13.6V
27.2V

LOW

TRIGGER

12.8V
25.6V

HIGH

TRIGGER

14.6V
29.2V

OVER VOLTAGE

FAULT

15.2V
30.4V