INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the ILB-CP-HE
unit connector is disconnected.
1. FIXTURE
The
ILB-CP-HE
can be used with most LED loads that operate at 10-60 VDC. See the
ILB Model Specification
Chart
for output specifications of the unit being installed.
1. The ILB-CP-HE series has been evaluated to and found compliant to UL standard 924. The as-installed
performance of system must meet or exceed all Federal, State, and Local code requirements.
2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels.
2. MOUNTING THE ILB-CP-HE
The
ILB-CP-HE
should be mounted on or nearby the fixture above the ceiling. The flex conduit marked “A” should
be wired into the driver/lamp compartment or to an electrical junction box on the fixture which allows access to the
fixture connections. Refer to
Illustration 1
for typical mounting.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the load.
ILB-CP05
ILB-CP07
ILB-CP10
5 WATTS
7 WATTS
10 WATTS
ILB MODEL SPECIFICATION CHART
OUTPUT POWER (CONSTANT)
ILB-CP12
12 WATTS
3. WIRING
Refer to Illustration 2 for the appropriate wiring of the LED load and driver. Install in accordance with the
National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
Illustration 1 Downlight Fixture
FLEX “A”
JUNCTION
BOX
CEILING
TILE
A.C. BALLAST &
LAMP SOCKET COMPARTMENT
FLEX “B”
SWITCH BOX
TEST SWITCH
CHARGE LIGHT
ILB-CP-HE
TEST
ACCESSORIES
LED FIXTURE
TBTS