INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off and the ILB-CP-HE 
unit connector is disconnected.

1. FIXTURE

The 

ILB-CP-HE

 can be used with most LED loads that operate at 10-60 VDC. See the 

ILB Model Specification

Chart

 for output specifications of the unit being installed.

1. The ILB-CP-HE series has been evaluated to and found compliant to UL standard 924. The as-installed

performance of system must meet or exceed all Federal, State, and Local code requirements.

2. Refer to Addendum 11042014 for detailed specifications and methods to calculate emergency light levels.

2. MOUNTING THE ILB-CP-HE

The 

ILB-CP-HE

 should be mounted on or nearby the fixture above the ceiling. The flex conduit marked “A” should

be wired into the driver/lamp compartment or to an electrical junction box on the fixture which allows access to the
fixture connections. Refer to 

Illustration 1

 for typical mounting.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the load.

ILB-CP05

ILB-CP07

ILB-CP10

5 WATTS

7 WATTS

10 WATTS

ILB MODEL SPECIFICATION CHART

OUTPUT POWER (CONSTANT)

ILB-CP12

12 WATTS

3. WIRING

Refer to Illustration 2 for the appropriate wiring of the LED load and driver. Install in accordance with the

National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

Illustration 1          Downlight Fixture

FLEX “A”

JUNCTION

BOX

CEILING

TILE

A.C. BALLAST &

LAMP SOCKET COMPARTMENT

FLEX “B”

SWITCH BOX

TEST SWITCH

CHARGE LIGHT

ILB-CP-HE

TEST 

ACCESSORIES

LED FIXTURE

TBTS