INSTALLATION INSTRUCTIONS

CAUTION:   Before installing, make certain the A.C. power is off and the IIS-50-I unit connector 
is disconnected.

1.  MOUNTING THE IIS-50-I

     Mount the 

IIS-50-I on or adjacent to the fixture in a position that does not interfere with the existing A.C. driver, ballast or 

any other hardware. Extend the flex conduit to the junction box or wireway channel and punch a 

7

/

8

 hole. Feed the wires 

and flex connector down through the hole in the fixture and secure in place with the flex connector nut. An optional T-bar 
mounting kit is available to mount the 

IIS-50-I above the ceiling tile adjacent to the fixture. Refer to Illustration 1. To order 

the optional T-bar mounting kit (part number TBMK-160) contact Customer Service.

    When remote mounting, consult Customer Service for the maximum allowable distance between the inverter and fixture.

  

CAUTION: Properly secure the IIS-50-I in the ceiling grid to insure compliance with local, state, and federal 
guidelines regarding ceiling mounted equipment.

2. WIRING
  

A. CONNECTING THE INVERTER AC INPUT

  This is the AC input that charges the inverter battery, therefore it requires an unswitched AC supply. For 120V supply, 

connect the AC line wire to the BLACK lead. 

For 277V supply, connect the AC line wire to the ORANGE lead.  Connect 

the WHITE to the AC Neutral. Refer to the Wiring Diagram on Page 4. 

CAUTION: Cap the unused BLACK or ORANGE 

input wire. Failure to do so may result in equipment failure and void the warranty.

    B. CONNECTING THE NORMAL AC SWITCHED / UNSWITCHED SUPPLY

  Connect the BLK/ORG lead to the switched or unswitched AC supply. Connect the WHT/BLU to the AC Neutral. Refer 

to the Wiring Diagram on Page 4. For Emergency Only (Normally Off) operation, the BLK/ORG and WHT/BLU leads 
are not used and should be capped separately.

    Select the appropriate output voltage to the AC driver/ballast on the AC Output Setting (

Voltage Selector) switch (120 

or 277 volts) located on the flex end of the 

IIS-50-I. Refer to Illustration 2.

    C. CONNECTING THE INVERTER TO THE AC FIXTURE

  Connect the output leads of the IIS-50-I to the AC fixture. When making connections to the IIS-50-I, do NOT con-

nect the input neutral WHITE or WHT/BLU to the output neutral GRAY. Refer to the Wiring Diagram on Page 4. 
For additional wiring diagrams consult Customer Service.

    Wire the AC driver/ballast with the lamp(s) in accordance with the manufacturer’s installation instructions.

  

Install in accordance with the National Electrical Code and local regulations.

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

OPTIONAL T-BAR MOUNTING KIT

CEILING T-GRID

FIXTURE

36-INCH FLEXIBLE

CONDUIT

FIXTURE

JUNCTION BOX

OR

WIRING 

COMPARTMENT

SWITCH BOX FOR

TEST ACCESSORIES

(BOX NOT SUPPLIED)

FLEXIBLE CONDUIT

TO TEST ACCESSORIES

(NOT SUPPLIED)

Illustration 1: IIS-50-I and Test Accessory Mounting (Top View)

IIS-50-I

AC OUTPUT

(”VOLTAGE SELECTOR”)

SWITCH

Illustration 2: AC Output Setting

IIS-50-I  

(End View)

CAUTION: Confirm that the AC Output Switch 
(“Voltage Selector”)  is in the proper position 
and that all wiring is complete before supplying 
AC power.