30ACi+, 30ACi Deluxe,  

35ACi+ and 35ACi Deluxe

Battery Backup System

Register your product at www.sumpro.com

b.  Possible loose AC output connection.

i.  Check all AC output connections.

ii.  Check main 15 amp circuit breaker to 

the wall outlet.

7.  Low Surge Power 

a.  Possible weak batteries or battery cables 

are too long.

i.  Refer to cable and battery 

recommendation in this manual.

8.  Inverter Overheats

a.  Inverter is hot.

i.  Reduce load and let the inverter cool 

down. 

9.  If Pump Does Not Run and Hums

a.  Inverter circuit breaker is off.

b.  Water level in sump has not reached turn-

on level. 

c.  Pump cord is not making contact in 

receptacle.

d.  Switch may not be working properly. 

i.  Plug pump directly into wall outlet 

without the switch plug. If pump runs, 

the switch may need to be replaced. 

e.  If all of the above are OK, then the motor 

could be malfunctioning.

10.  Pump Runs but Does Not Deliver Water 

a.  Check valve is installed backwards. Arrow 

on valve should point in direction of flow.

b.  Discharge shut-off valve (if used) may be 

closed.

c.  Impeller or volute openings are fully or 

partially clogged. Remove pump and clean.

d.  Pump is air-locked. Start and stop several 

times by plugging and unplugging cord. 

Check for clogged vent hole in pump case. 

Drill a 1/8 inch hole into PVC pipe. 

e.  Inlet holes in pump base are clogged. 

Remove pump and clean the openings.

f.  Vertical pumping distance is too high. 

Reduce distance or change the discharge 

fittings of the pump. 

11.  Pump Runs and Pumps Out Sump but Does 

Not Stop

a.  Unplug the pump/switch plug from the 

inverter.

b.  Plug the pump back into the switch plug 

and plug the switch plug into a wall outlet.

i.  If the pump does not turn on right 

away, and the water level is not at the 

On level, let the pump go through an 

On / Off cycle a few times to insure 

that the switch is functioning properly. 

The  basin  may  need  to  be  filled  with 

a garden hose or bucket.  Plug pump/

switch plug back into one outlet on the 

inverter and test again.

ii.  If the pump turns on right away, and 

the water level is not at the On level, 

the switch may have to be replaced. 

12. Pump Runs but Only Delivers a Small 

Amount of Water 

a.  Pump may be air-locked. Start and stop 

several times by plugging and unplugging 

cord. Check for clogged vent hole in pump 

case. Drill a 1/8 inch hole into PVC pipe.

b.  Vertical pumping distance may be too high. 

Reduce distance or change the discharge 

fitting of the pump. Inlet holes in pump base 

are clogged. Remove pump and clean the 

strainer and openings. 

c.  Impeller or volute openings may be fully or 

partially clogged. Remove pump and clean.

d.  Pump impeller is partially clogged with tar 

or paint, causing motor to run slow and 

overload Remove pump and clean.

Содержание 30ACi Deluxe

Страница 1: ... TW20354 30ACi Deluxe 1 600 va Inverter PN TW20313 2 Battery Box PN EP0 300 3 2 WC33M PN M5235033MN 4 Ion Genesis PN iNG2 10 1B 5 Battery Leads PN TW20354 35ACi 1 800 va Inverter PN TW20315 2 Battery Box PN EP0 300 3 BA33M PN HP20180 4 Ion Switch Alarm PN iNP20306 5 Ion Pipe Mount Bracket PN iN SPB 1 6 Battery Leads PN TW20354 35ACi Deluxe 1 800 va Inverter PN TW20315 2 Battery Box PN EP0 300 3 2 ...

Страница 2: ...park able electrical devices or open flame when working on this unit WARNING Do not install unit in locations classified as hazardous per N E C ANSI NFPA 70 1999 FAILURE TO HEED ABOVE CAUTIONS COULD RESULT IN INJURY OR DEATH WARNING These systems are designed to operate only one pump at a time the one s supplied with the unit Using anything other than the pump supplied with the system will cause d...

Страница 3: ...c CAUTION The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes It is electrically conductive and corrosive The following procedures should be observed a If electrolyte contacts the skin wash it off immediately b If electrolyte contacts the eyes flush thoroughly and immediately with water Seek medical attention c Spilled electrolyte should be washed down with a suitable ac...

Страница 4: ...ting on DC Power 1 Follow Steps 1 4 above 2 Push and hold the Power button on the front of the inverter for 3 5 seconds Tools Needed A pipe wrench insulated pliers insulated adjustable wrench and insulated screwdriver will be needed Installation Instructions Remove all packing and contents from the battery box enclosure an inverter battery box pig tail with Anderson connector inverter power cord a...

Страница 5: ...ower is available the Power button is automatically on If the button is held in for 3 5 seconds while in AC mode the display will go blank and the inverter will be off The inverter can be turned back on by holding in the Power button again for 3 5 seconds or unplugging the inverter from the wall outlet for 10 seconds and plugging it back in Note The range of the switch is the distance between the ...

Страница 6: ... with AC power 120 volt The Anderson connector on the inverter leads gets connected to the Anderson connector on the Pig Tail coming from the battery Front Panel DC MODE AC MODE Output Voltage Output Voltage Amount of Load Amount of Load Battery Display Battery Display Charge in Batteries Charge in Batteries Frequency Load Amps Input Voltage Load Amps Pump Outlet Main Circuit Breaker Quick Connect...

Страница 7: ... Boost Voltage 13 7 0 2 V Overload 130 3 With Auto Reset Function 30ACi 30ACi Deluxe 35ACi 35ACi Deluxe Inverter Specifications Inverter Specifications Model Output HP Amp Voltage WC33 1 3 4 0 115 Pump Specifications Model Output HP Amp Voltage BA33 1 3 4 5 115 Pump Specifications Technical Specifications 30ACi 30ACi Deluxe Pump Performance Curve 35ACi 35ACi Deluxe Pump Performance Curve 30ACi 30A...

Страница 8: ... pump or switch Troubleshooting 1 Fan keeps turning on in AC mode a This is a normal function of the unit Every hour the unit checks the batteries and its functions During this time the fan may run for 1 10 minutes to keep the internal electronics cool 2 Inverter Mode but No Power a Check display to see if a low battery condition is present Remove all loads unplug the AC power cord for 10 sec and ...

Страница 9: ...gged vent hole in pump case Drill a 1 8 inch hole into PVC pipe e Inlet holes in pump base are clogged Remove pump and clean the openings f Vertical pumping distance is too high Reduce distance or change the discharge fittings of the pump 11 Pump Runs and Pumps Out Sump but Does Not Stop a Unplug the pump switch plug from the inverter b Plug the pump back into the switch plug and plug the switch p...

Страница 10: ...otor stator may be defective 15 Pump Does Not Turn On a Test the pump without the Ion switch alarm i Plug the pump directly into a wall outlet without plugging it into the Ion switch alarm plug ii If pump still does not run the pump may be defective iii If the pump does run continue to the next step b Test the Ion switch alarm with the pump i Plug the pump into the Ion switch alarm and plug the Io...

Страница 11: ...OPERATION MANUAL Dated 02 10 2015 Document Name 30 35ACi Deluxe_OM Page 11 of 12 30ACi 30ACi Deluxe 35ACi and 35ACi Deluxe Battery Backup System Register your product at www sumpro com Notes ...

Страница 12: ...ropolitan to correct a defect in a product shall extend the Warranty beyond the period set forth above Metropolitan shall not be obligated to remedy any defect where otherwise required pursuant to the Warranty unless and until Buyer notifies Metropolitan in writing of the defect and then only if such notification is made prior to the expiration of the period set forth above 3 Process of Claims and R...

Отзывы: