INSTALLING AND WIRING THE ZP3-HPS-ESP  

WIRING THE TRANSFORMER:

Wire the separate 24 Volt transformer to the
24VAC  POWER  ‘R’  and  ‘C’  terminals.  Use 
conventional  18-2  thermostat  wire.  After 

removing  the  outer  jacket,  strip  approximately 
1/8” insulation off of each wire. Land each lead to 
the 24VAC POWER screw terminals marked C 
and R.

WIRING  THE  ZPA-OTS  OUTDOOR  SENSOR 
FOR  HIGH  AND  LOW  BALANCE  POINT 

CONTROL:

The balance point feature can be used for both 
conventional or fossil fuel applications allowing 
up to 2 stages of cooling and 3 stages of heating. 

For fossil fuel systems having a 2 stage furnace, 
‘W1’ and ‘W2’ are jumpered at the furnace. This 
method  utilizes  the  internal  furnace  upstage 

timer  to bring on second stage fossil fuel. The 
ZPA-OTS Outdoor Sensor can be used for both 
high and low balance point control by adjusting 
the  onboard  balance  point  dials  on  the  panel. 

High BP is adjustable from 45° F to 65° F. Low BP 
is adjustable from 0° F to 40° F. If the outdoor 
temperature goes above the High BP setting, the 

system will not stage auxiliary heat. If the outdoor 
temperature falls below the Low BP setting, only 
the auxiliary heat source will be used.   High BP 
can  be  overridden  by  placing  any  zone 

thermostat in the emergency heat mode. 

Mount the sensor inside the heat pump cabinet 

to  avoid  direct  sunlight,  freezing  rain  or  snow.   
The  sensor  requires  separate  18-2  thermostat 
wire. Connect the sensor leads using wire nuts.   
Land  the  other  end  to  the  SENSOR  screw 

terminals marked OT on the panel. 

TEST, CHECK AND STARTUP:

1.  Verify  that  all  component  wires  have  been 
connected to the proper terminals and are secure.
2. Make sure that the selector switches on the

panel are in their proper  position  for  the specific 
application.
3.  Apply 24 Volt power to the panel. 
4. Place all zone thermostats in the OFF mode with 

Auto fan.
5. With no calls taking place, the following panel 
LEDs should be lit:  

         

    24V  

 

    LIMIT 

 

    ZD1 

 

    ZD2 

 

    ZD3
6. Visually confirm that all zone dampers are in the 
open position.

7. Place zone 1 thermostat in the continuous fan 
ON mode and the system blower should come on. 
The following panel LEDs should be lit:
   24V  

 

  

    G   

 

    LIMIT
    ZD1

Note:  If  system  static  pressure  goes  above 
setpoint, the SPS LED will light along with the non-
calling zone LEDs until non-calling zone dampers   
modulate to relieve the static pressure then both 

LEDs will turn off.
8. Put zone 1 thermostat in Auto fan and repeat the 
same steps for zone 2 and zone 3. The only change 

in LED status will be ZD2 LED will light for zone 2 
and ZD3 LED will light for zone 3.
9. Once the ventilation test is completed, and the 
zone thermostat fan modes are set to Auto, place 

zone 1 thermostat in the cooling mode and adjust 
the setpoint above the space temperature until it 
calls  for  cooling.  Keep  in  mind  that  the  zone 

thermostat may have a time delay and that the
panel has a 3 minute short cycle time delay before 
allowing  the  equipment  to  come  on.  Once  the 
cooling  cycle  is  energized,  the  following  panel 

LEDs should be lit: 
    24V  

 

 

    Y1

    G
    O/B (If reversing valve = O cooling)
    LIMIT
    ZD1  

6

Содержание ZP3-HPS-ESP

Страница 1: ...will changeover and take care of the opposite call If zones being served heating or cooling have not been satisfied within 20 minutes while an opposite call is taking place the system will changeover When the zone is satisfied or 20 minutes has elapsed the system will again changeover if an opposite call exists This is referred to as Auto Changeover First Call Priority Time Share In the event of a...

Страница 2: ...ED ZONE 3 DAMPER LED REVERSING VALVE LED O B REVERSING VALVE SWITCH CONVENTIONAL HEAT PUMP OR FOSSIL FUEL SWITCH 3 AMP 3 AMP 302HP ZONE 2 THERMOSTAT ZONE 2 DAMPER ZONE 3 THERMOSTAT ZONE 3 DAMPER HVAC UNIT TERMINALS DISCHARGE TEMPERATURE SENSOR OUTDOOR SENSOR USED FOR HIGH LOW BALANCE POINT CONTROL STATIC PRESSURE SENSOR LED STATIC PRESSURE SENSOR TERMINALS LOW BP LED LOW BP SETPOINT DIAL SPEED UP ...

Страница 3: ...2ND STAGE COMPRESSOR G FAN O B REVERSING VALVE POWER CLOSE COMMON POWER OPEN C 24V COMMON R 24V HOT W AUXILIARY HEAT Y1 1ST STAGE COMPRESSOR Y2 2ND STAGE COMPRESSOR G FAN O B REVERSING VALVE POWER CLOSE COMMON POWER OPEN R 24V HOT W AUXILIARY HEAT Y1 1ST STAGE COMPRESSOR Y2 2ND STAGE COMPRESSOR G FAN O B REVERSING VALVE WIRE TO ESP 400 PS PRESSURE SENSOR WIRE TO ZPA DST DISCHARGE TEMPERATURE SENSO...

Страница 4: ...BP is adjustable from 0 F to 40 F High and Low balance point control can be used for both conventional heat pumps and fossil fuel systems If the outdoor temperature goes above the High BP setting the system will not stage auxiliary heat If the outdoor temperature falls below the Low BP setting only the auxiliary heat source will be used High BP can be overridden by placing any zone thermostat in t...

Страница 5: ...WIRING THE ZPA DTS DISCHARGE TEMPERATURE SENSOR Drill a 15 32 hole in the middle of the main discharge air plenum approximately 18 to 30 from the heat pump electric strip heater or the furnace heat exchanger in a fossil fuel application Slide the discharge air probe into the hole and use two self tapping sheet metal screws to secure the base to the plenum Use conventional 18 2 thermostat wire and ...

Страница 6: ...wire nuts Land the other end to the SENSOR screw terminals marked OTon the panel TEST CHECK AND STARTUP 1 Verify that all component wires have been connected to the proper terminals and are secure 2 Make sure that the selector switches on the panel are in their proper position for the specific application 3 Apply 24 Volt power to the panel 4 Place all zone thermostats in the OFF mode with Auto fan...

Страница 7: ... low limit 20 minute time share Purge ON 1 minute Thermostats Single or multi stage heat pump Programmable or non programmable Auto or manual changeover Sensors iO ZP3 DAS Discharge Air Sensor NTC Type 3 10K 77 F 3 77 F Ω iO ZP3 OT Outdoor Sensor NTC Type 3 10K 77 F 3 77 F Ω FIELD WIRING TERMINALS Zone Thermostats C 24Vac Common R 24Vac Hot W Auxiliary or Emergency Heat Y1 First Stage Compressor Y...

Страница 8: ...ans DSI controls generate electromagnetic interference EMI during their trial for ignition This electronic noise can sometimes interfere with ESP zoning panels as well as other nearby electronic components and even with the ignition control itself When using an ESP zoning panel with a gas furnace having DSI we recommend that the panel be mounted at least ten feet away from the furnace to reduce an...

Отзывы: