As a terminal dedicated to user programming, PORT0 can be
converted to programming protocol through the mode selection switch.
The relationship between PLC operation status and the protocol used
by PORT0 is shown in the following table.
Mode selection
switch position
status
PORT0 operation protocol
ON
Running
Programming protocol, or Modbus protocol,
or free-port protocol, or N: N network
protocol, as determined by user program and
system configuration
ON
TM
Running
Converted to programming protocol
OFF
TM
Stop
OFF
Stop
If the system configuration of user program is
free-port protocol, it converts to programming
protocol automatically after stop; or system
protocol keeps unchanged
PORT1
、
PORT2 are ideal for connection with equipment that can
communicate (such as inverters). With Modbus protocol or RS485
terminal free protocol, it can control multiple devices through the
network. Its terminals are fixed with screws. You can use a shielded
twisted-pair as the signal cable to connect communication ports by
yourself.
5 Installation
PLC is applicable to Installation category II, Pollution degree 2.
5.1 Installation Dimensions
型号
长
宽
高
净重
IVC1L-0806MAR
、
IVC1L-0806MAT
135mm
90mm
71.2mm
440g
IVC1L-1208MAR
、
IVC1L-1208MAT
440g
IVC1L-1410MAR
、
IVC1L-1410MAT
、
470g
IVC1L-1614MAR
、
IVC1L-1614MAT
150mm
90mm
71.2mm
650g
IVC1L-2416MAR
、
IVC1L-2416MAT
、
IVC1L-1614MAR1
、
IVC1L-1614MAT1
、
182mm
90mm
71.2mm
750g
IVC1L-3624MAR
、
IVC1L-3624MAT
224.5mm
90mm
71.2mm
950g
5.2 Installation Method
DIN rail mounting
Generally you can mount the PLC onto a 35mm-wide rail (DIN), as
shown in the following figure.
Screw fixing
Fixing the PLC with screws can stand greater shock than DIN rail
mounting. Use M3 screws through the mounting holes on PLC
enclosure to fix the PLC onto the backboard of the electric cabinet, as
shown in the following figure.
5.3 Cable Connection And Specification
Connecting power cable and grounding cable
The connection of AC power and auxiliary power is demonstrated in the
following figure.
We suggest you wire a protection circuit at the power supply input
terminal.See the figure below.
COM
24V
N
PG
L
开关电源
S/S
X0
X7
IVC1L-1614MAR
Xn
Xm
S/S
IVC1-
0808ERN
AC - L
+24V
+5V
GND
COM
24V
PG
IVC 1-4AD
IVC 1-4DA
IVC 1-5AM
IVC 1-4TC
AC - N
Connect the PLC
terminal to the grounding electrode. To ensure
reliable grounding cable connection, which makes the equipment safer
and protects it from EMI.use AWG12~16 cable, and make the cable as
short as possible. Use independent grounding. Avoid sharing route with
the grounding cable of other equipment (particularly those with strong
EMI). See the following figure.
Cable specification
When wiring a PLC, use multi-strand copper wire and ready-made
insulated terminals to ensure the quality. The recommended model and
the cross-sectional area of the cable are shown in the following table.
Wire
Cross-sectional
area
Recommended
model
Cable lug and
heat-shrink tube
AC power
cable (L, N)
1.0~2.0mm
²
AWG12, 18
H1.5/14 round insulated
lug, or tinned cable lug
Earth cable
(
)
2.0mm
²
AWG12
H2.0/14 round insulated
lug, or tinned cable end
Input signal
cable (X)
0.8~1.0mm
²
AWG18, 20
UT1-3 or OT1-3
solderless lug
Φ3 or Φ
4
heat shrinkable
tube
Output signal
cable (Y)
0.8~1.0mm
²
AWG18, 20
Fix the prepared cable head onto the PLC terminals with screws.
Fastening torque: 0.5~0.8Nm.
The recommended cable processing-method is shown in the following
figure.
PLC
PLC
Other
equipment
Other
equipment
PLC
Other
equipment
Best
Good
Bad