IPE300 series engineering VFD
Installation guidance
-16-
4 Installation guidance
4.1 What this chapter contains
This chapter describes the mechanical installation and electrical installation of the VFD.
Only trained and qualified professionals are allowed to carry out the operations
mentioned in this chapter. Please carry out operations according to instructions
presented in "Safety precautions". Ignoring these safety precautions may lead to
physical injury or death, or device damage.
Ensure the VFD power has been disconnected before installation. If the VFD
has been powered on, disconnect the VFD power and wait for at least the time
specified on the VFD, and ensure the POWER indicator is off. You are
recommended to use a multimeter to check and ensure the VFD DC bus voltage
is below 36V.
The VFD installation must be designed and done according to applicable local
laws and regulations. INVT does not assume any liability whatsoever for any
VFD installation which breaches local laws or regulations. If recommendations
given by INVT are not followed, the VFD may experience problems that the
warranty does not cover.
4.2 Mechanical installation
4.2.1 Installation environment
The installation environment is essential for the VFD to operate with best performance in the long run.
Install the VFD in an environment that meets the following requirements.
Environment
Condition
Installation
site
Indoor
Ambient
temperature
-10
–+50°C
When the ambient temperature exceeds 40°C, derate 1% for every increase of
1°C.
Do not use the VFD when the ambient temperature exceeds 50°C.
In order to improve reliability, do not use the VFD in the places where the
temperature changes rapidly.
When the VFD is used in a closed space, such as control cabinet, use a
cooling fan or air conditioner for cooling, preventing the internal temperature
from exceeding the temperature required.
When the temperature is too low, if you want to use the VFD that has been
idled for a long time, install an external heating device before the use to
eliminate the freeze inside the VFD. Otherwise, the VFD may be damaged.