Goodrive350-19 series VFD for crane
Function parameter list
-272-
Function
code
Name
Description
Default
Modify
Select corresponding acceleration/deceleration
time, and then convert 16-bit binary number into
hexadecimal number, finally, and then set
corresponding function codes.
ACC/DEC time 1 is set by
ACC/DEC time 2 is set by
ACC/DEC time 3 is set by
ACC/DEC time 4 is set by
Setting range: 0x0000
–0xFFFF
P10.36 PLC restart mode
0: Restart from the first step, namely if the VFD
stops during running (caused by stop command,
fault or power down), it will run from the first step
after restart.
1: Continue running from the step frequency
when interruption occurred, namely if the VFD
stops during running (caused by stop command
or fault), it will record the running time of current
step, and enters this step automatically after
restart, then continue running at the frequency
defined by this step in the remaining time.
0
◎
P10.37
Multi-step time
unit
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
0
◎
P11 group
––Protection parameters
Function
code
Name
Description
Default
Modify
P11.00
Protection against
phase loss
0x000
–0x1111
Ones place: Reserved
Tens place:
0: Disable output phase loss protection.
1: Enable output phase loss protection.
Hundreds place:
0: Disable hardware input phase loss protection.
1: Enable hardware input phase loss protection.
Thousands place:
0: During stop, if a hardware input phase loss
Model
depended
○