Goodrive350-19 series VFD for crane
Function parameter list
-208-
Function
code
Name
Description
Default
Modify
source
2: (A+B)
3: (A-B)
4: Max(A, B)
5: Min(A, B)
P00.10
Frequency set
through keypad
When A and B frequency commands select the
keypad for setting, the value is the original
setting one of the frequency data of VFD.
Setting range: 0.00 Hz
(Max. output
frequency)
50.00Hz
○
P00.11
ACC time 1
ACC time means the time needed if the VFD
speeds up from 0Hz to the max. output
frequency (
). DEC time means the time
needed if the VFD speeds down from the max.
output frequency (
) to 0Hz. The VFD has
four groups of ACC/DEC time, which can be
selected by P05. The factory default ACC/DEC
time of the VFD is the first group.
setting range: 0.0
–3600.0s
Model
depended
○
P00.12
DEC time 1
Model
depended
○
P00.13 Running direction
0: Run at the default direction.
1: Run at the opposite direction.
2: Disable reverse running
Note: It can be modified only when
is 1
indicating special functions are enabled.
0
○
P00.14 Carrier frequency
Carrier
frequency
Electro magnetic
noise
Noise and leakage
current
Cooling
level
High
Low
High
Low
High
Low
1kHz
10kHz
15kHz
Mapping between models and carrier
frequencies:
Model
Default carrier
frequency
380V
0.4
–11kW
4kHz
>15kW
1.5kHz
660V
22
–55kW
4kHz
Model
depended
○