Goodrive20-EU Series VFD
Function parameters
-40-
Function
code
Name
Description
Default Modify
3: Function code locking (lock all function codes)
4: Reserved
5: Restore the default value (factory test mode)
6: Restore the default value (including the motor
parameters)
Note:
1. After the selected operation is performed, the
function code is automatically restored to 0.
Restoring default values may delete the user
password. Exercise caution when using this
function.
2. Restoring default values (factory test mode)
will restore the parameters to the corresponding
standard
version.
Non-professionals
shall
exercise caution when using this function.
P01 group Start and stop control
Function
code
Name
Description
Default Modify
P01.00
Start mode
0: Start-up directly: start from the starting
frequency P01.01
1: Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2
The direction and speed will be tracked
automatically for the smoothing starting of
rotating motors. It suits the application with
reverse rotation when big load starting.
Note:
This function is only available for the
VFDs≥4kW.
0
◎
P01.01
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the
original frequency during the VFD starting. See
P01.02 for detailed information.
Setting range: 0.00
–50.00Hz
0.50Hz
◎