Goodrive350A series high-performance multifunction VFD
Function parameter list
-167-
Function
code
Name
Description
Default
Modify
Setting range: 0.0
–3600.0s
P04.31 Max. output voltage Used to set the upper and lower limits of
output voltage.
Vmax
Vmin
V set
Time t
t1
t2
t1=P04.29
t2=P04.30
Setting range of P04.31: P04.32
–100.0% (of
the motor rated voltage)
Setting range of P04.32: 0.0%
100.0%
◎
P04.32 Min. output voltage
0.0%
◎
P04.33
Weakening
coefficient in
constant power
zone
1.00
–1.30
1.00
○
P04.34
Pull-in current 1 in
SM V/F control
When the SM V/F control mode is enabled,
the function code is used to set the reactive
current of the motor when the output
frequency is lower than the frequency
specified by P04.36.
Setting range: -100.0%
–100.0% (of the motor
rated current)
20.0%
○
P04.35
Pull-in current 2 in
SM V/F control
When the SM V/F control mode is enabled,
the function code is used to set the reactive
current of the motor when the output
frequency is higher than the frequency
specified by P04.36
Setting range: -100.0%
–100.0% (of the motor
rated current)
10.0%
○
P04.36
Frequency
threshold for pull-in
current switching in
SM V/F control
When the SM V/F control mode is enabled,
the function code is used to set the frequency
threshold for the switching between pull-in
current 1 and pull-in current 2.
Setting range: 0%
–200.0% (of the motor
rated frequency)
20.0%
○
P04.37
Reactive current
When the SM V/F control mode is enabled,
50
○