GD310-UL series VFD
Function parameter
-51-
Function
code
Name
Description
Default
value
Modify
stand-by state and wait for the delay time set by
P01.23
Setting range: 0.0
–60.0s
P01.24
Delay time of
the stop speed
Setting range: 0.0
–100.0 s
0.0s
○
P01.25
0Hz output
selection
Select the output mode at 0Hz.
0: Output without voltage
1: Output with voltage
2: Output at DC braking current at stopping
0
○
P02 Group Motor 1
Function
code
Name
Description
Default
value
Modify
P02.00
Motor type 1
0: Asynchronous motor
1: Synchronous motor
Note
: Switch the current motor by the switching
channel of P08.31.
0
◎
P02.01
Rated power
of AM 1
0.1
–3000.0kW
Depend
on model
◎
P02.02
Rated
frequency of
AM 1
0.01Hz
–P00.03 (the max frequency)
60.00Hz
◎
P02.03
Rated speed
of AM 1
1
–36000rpm
Depend
on model
◎
P02.04
Rated voltage
of AM 1
0
–1200V
◎
P02.05
Rated current
of AM 1
0.8
–6000.0A
◎
P02.06
Stator resistor
of AM 1
0.001
–65.535Ω
○
P02.07
Rotor resistor
of AM 1
0.001
–65.535Ω
○
P02.08
Leakage
inductance of
AM 1
0.1
–6553.5mH
○
P02.09
Mutual
inductance of
AM 1
0.1
–6553.5mH
○
P02.10
Non-load
current of AM 1
0.1
–6553.5A
○
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...