GD310-UL series VFD
Basic operation instruction
-162-
7.15.1 General steps of PID parameters setting:
a)
Ensure the gain P
When ensure the gain P, firstly cancel the PID integration and derivation (set Ti=0 and Td=0, see the
PID parameter setting for detailed information) to make proportional adjustment is the only method to
PID. Set the input as 60%
–70% of the permitted Max. Value and increase gain P from 0 until the
system vibration occurs, vice versa, and record the PID value and set it to 60%
–70% of the current
value. Then the gain P commissioning is finished.
b) Ensure the integral time Ti
After ensuring the gain P, set an original value of a bigger integral time and decrease it until the
system vibration occurs, vice versa, until the system vibration disappear. Record the Ti and set the
integral time to 150%
–180% of the current value. Then integral time commissioning is finished.
c) Ensure the derivative time Td
Generally, it is not necessary to set Td which is 0.
If it needs to be set, set it to 30% of the value without vibration via the same method with P and Ti.
d)
Commissioning the system with and without load and then adjust the PID parameter until it is
available.
7.15.2 PID inching
After setting the PID control parameters, inching is possible by following means:
Control the overshoot
Shorten the derivative time and prolong the integral time when overshoot occurs.
Before adjustment
After adjustment
Response
Time
Before adjustment
After adjustment
Response
Time
Before adjustment
After adjustment
Time
Response
Before adjustment
After adjustment
Response
Time
Achieve the stable state as soon as possible
Shorten the integral time (Ti) and prolong the derivative time (Td) even the overshoot occurs, but the
control should be stable as soon as possible.
Содержание GD310-011P-4-UL
Страница 1: ......
Страница 269: ...6 6 0 0 1 0 0 3 9 3 ...