Goodrive300-01A series VFD for air compressor
Function description
-86-
Function
code
Name
Description
Default
Modify
P18.28
0
150
P17.20
-20
PT1 input
voltage
Present temperature
P19.12
P18.29
P18.32
0
150
P17.22
-20
PT2 input
voltage
Present temperature
P19.12
P18.33
P18.03=0
P18.03=1
20
120
120
20
Range: -20
–150
℃
P19.13
Signal state 1
0000
–0xFFFF
BIT0: Air filter blockage signal
1: Fault; 0: Normal
BIT1: Oil filter blockage signal
1: Fault; 0: Normal
BIT2: Separator blockage signal
1: Fault; 0: Normal
BIT3: Precision splitter blockage signal
1: Fault; 0: Normal
BIT4: External fault signal 1
1: Fault; 0: Normal
BIT5: External fault signal 2
1: Fault; 0: Normal
BIT6: Solenoid valve signal state
1: Load; 0: Unload
BIT7: Fan state
1: Run; 0: Stop
BIT8: Pressure pre-alarm signal
1: Pressure pre-alarm; 0: Normal
BIT9: Temperature pre-alarm signal
1: Temperature pre-alarm; 0: Normal
BIT10: Pressure alarm signal
1: Pressure alarm; 0: Normal
BIT11: Temperature alarm signal
1: Temperature alarm; 0: Normal
0
●