GD200A series VFD
Function parameters
-48-
Function
code
Name
Description
Default
value
Modify
1
5
12
60
116%
200%
Time (min)
Current overload
multiple
150%
180%
Setting range: 20.0%
–120.0%
P02.28
Correction
coefficient of
motor 1 power
Correct the power displaying of motor 1.
Only impact the displaying value other than the
control performance of the VFD.
Setting range: 0.00
–3.00
1.00
●
P03 Group Vector control
Function
code
Name
Description
Default
value
Modify
P03.00
Speed loop
proportional
gain1
The parameters
vector control mode. Below the switching
frequency 1 (P03.02), the speed loop PI
parameters are:
and
. Above the
switching frequency 2 (
), the speed loop PI
parameters are:
and
. PI
parameters are gained according to the linear
change of two groups of parameters. It is shown
as below:
PI parameters
Output frequency
(P03.00,P03.01)
(P03.03,P03.04)
P03.02
P03.05
Setting the proportional coefficient and integral
time of the adjustor can change the dynamic
response performance of vector control speed
loop. Increasing the proportional gain and
decreasing the integral time can speed up the
dynamic response of the speed loop. But too high
20.0
○
P03.01
Speed loop
integral time1
0.200s
○
P03.02
Low switching
frequency
5.00Hz
○
P03.03
Speed loop
proportional
gain 2
20.0
○
P03.04
Speed loop
integral time 2
0.200s
○
P03.05
High switching
frequency
10.00Hz
○